24/84
Memory organisation
List of events
© Landis+Gyr
In the dedicated event logs, important information can be stored per entry
such as:
Duration of the events
Extreme values of the events (not for missing voltage).
Instantaneous values
Maximum three energy registers
Additional information can be read from the header of the event logs, such
as the longest entry, the shortest entry, the total number of occurrence and
the total duration of the event.
The dedicated event logs are organised as circular buffers, i.e. the oldest
entry will be overwritten by the most recent entry.
The table below lists all events which can be captured in the event log.
Depending on the parameterisation, some events may never occur.
Events which can be stored in the dedicated event log are marked in the
corresponding column.
Number
Event
2
All energy registers cleared
3
Stored values and/or load profile cleared
4
Event log profile cleared
5
Battery voltage low
7
Battery ok
8
Billing period reset
9
Daylight saving time enabled or disabled
10
Clock adjusted (old time/date)
11
Clock adjusted (new time/date)
17
Under-voltage L1
18
Under-voltage L2
19
Under-voltage L3
20
Over-voltage L1
21
Over-voltage L2
22
Over-voltage L3
23
Power down
24
Power up
25
Over-current L1
26
Over-current L2
27
Over-current L3
28
Over-current neutral
31
Power factor monitor 1
32
Power factor monitor 2
33-40
Demand monitors 1-8
45
Error register cleared
D000030108 en m – E650 Series 3 – ZMD300AT/CT – User Manual
Device description
Entry in dedicated
event log possible
x
x
x
x
x
x