Outputs
Measuring system
Signal processing
Signal utilisation
© Landis+Gyr
Pulse inputs for connection of external pulse transmitters (only for
meters equipped with a communication unit)
The meter has the following outputs:
LCD display with buttons for local reading of billing data (single 8-digit
display with additional information, such as energy direction, energy
type, presence of phase voltages and identification number)
Optical test outputs (red, 1 in active energy meters, 2 in combi-meters)
Optional alert LED (red) to indicate alerts on the front face of the meter
Static relay with freely parameterised signal assignment (2 fixed, plus
up to 6 others on the extension board)
Relay outputs with limited parameterised signal assignment due to
limited life expectancy (up to 2 on the extension board)
Optical interface for automatic local data acquisition by a suitable
acquisition unit (handheld terminal)
Communication interfaces of various kinds in the communication unit
(also see section 2.7 "Communication" )
The input circuits (voltage dividers and current shunts with voltage trans-
former) record voltage and current in the individual phases. Analogue-
digital converters digitise these values and feed them as instantaneous
digital values via calibration stages to a signal processor.
The signal processor determines the following measured quantities from
the instantaneous digital values of voltage and current for each phase and
forms their mean value over one second:
Active power per phase
Reactive power per phase (combi-meters ZMD300CT only)
Phase voltages
Phase currents
Network (mains) frequency
Phase angles
For signal utilisation in the various registers, the microprocessor scans the
measured quantities every second to determine the following values:
Active energy (sum and individual phases, separated according to
energy direction, if required in the combi-meters ZMD300CT also
assigned to the 4 quadrants)
Reactive energy (only for combi-meters ZMD300CT, sum and
individual phases, separated according to energy direction, assigned
to the 4 quadrants)
Apparent energy (only for combi-meters ZMD300CT, sum and
individual phases, separated according to energy direction)
Power factor cosφ (only for combi-meters ZMD300CT, individual
phases and mean value)
Phase voltages
Phase currents and neutral current
D000030108 en m – E650 Series 3 – ZMD300AT/CT – User Manual