Table 53: Display only fields
Field/LED name
Surge Avoidance Surge Detected
(LED)
ACC Surge Detected (LED)
Stall Count
Stall Time ( __Days __Hrs __Min __Sec)
VGD Control State
Table 54: Programmable
Button
Extreme Stall Duration
PRV VGD Inhibit
PRV Offset
Surge React Time
Surge Wait Time
Stall Wait Time
Open Pulse
High Limit
Low Limit
Table 55: Navigation
V09 software
Button
and earlier
Home
Service
VGD
Service
70
Description
Illuminates momentarily when a surge is detected by the Surge Protection feature. If
equipped with a VSD or MV VSD, these are only the surges detected while the drive is
running at maximum frequency.
Only displayed if equipped with a VSD or MV VSD. Illuminates momentarily when a
surge is detected by the ACC function in the Microboard, while the drive is running at
less than maximum frequency.
Displays the number of times the Stall Detector Board output voltage goes above the
High Limit Setpoint. The count can be reset with an ADMIN access level password.
Displays the accumulated time the Stall Detector Board output voltage is greater than
the High Limit Setpoint while the chiller is running.
Displays the current state of the VGD control. The states are: Stall Waiting, Probing,
Stall Reacting, Surge Reacting, Surge Waiting, Hot Gas Hold, Hot Gas Over­ride, Sensor
Failure Override, Extreme Stall Override, Manual Hold, Manual Open, Manual Close.
Description
(10 to 20 minutes; default 10) – Specifies the maximum allowed time an extreme stall
condition can exist before the VGD operation is disabled and driven to the full open
position to protect it from damage.
(40% - 100% default 100%) – While the Pre-rotation Vanes position is greater than this
setpoint, extreme stall conditions are not checked, the VGD control is inhibited and the
VGD is pulsed open according to the Open Pulse Setpoint. While this is in effect, PRV
Position Override is displayed as Control Status.
(0 to 5%; default 3) – If the VGD control is in the Stall Waiting state and the Pre-rotation
Vanes position changes by more than this value, the Probing state will be entered.
If the PRV Offset is set to 0%, the Stall Waiting state is performed based only on the
Probe Wait Time setpoint interval.
(1 to 30 seconds; default 5) – Specifies the length of the close pulse applied to the VGD
in response to a surge.
(0.5 to 5 minutes; default 3) – Specifies how long the VGD control remains in the Surge
Waiting state before entering the Probing state.
(0.5 to 5 minutes; default 3) – Specifies how long the VGD control remains in the Stall
Waiting state before entering the Probing state.
(1 to 9 seconds; default 2) – Specifies the length of the open pulse applied to the VGD
during 10 second periods while in the Probing state.
(0.5 to 1.2 VDC; default 0.6 VDC; Specifies the Stall Detector Board output voltage that
represents an acceptable amount of stall noise.
(0.4 to 0.8 VDC; default 0.5 VDC; In the Stall Reacting State, the VGD is driven closed
until the Stall Detector Board output voltage decreases to this level.
V10 and later
with YORK
Description
Chiller Access
Manager
JCI Service
Returns user to Home screen.
JCI Service
Returns user to Variable Geometry Diffuser screen.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center