York YK Style H Operation Manual page 44

Centrifugal liquid chillers with optiview control center
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

Table 21: Display only fields
Field/LED name
Head Pressure Setpoint
Control Valve Command
Control Valve Control Mode
Table 22: Programmable
Button
Head Pressure Setpoint
Minimum Position
Shutdown Position
Control Valve Output Settings – Type
Control Valve Output Settings –
Direction
Control Valve Output Settings – Set
Control Valve Output Settings – Auto Places the Control Valve in automatic control.
Change Setpoints
Head Pressure Control – P
Head Pressure Control – I
Head Pressure Control – D
Table 23: Navigation
Button
Home
Condenser
44
Description
Displays the active Head Pressure Setpoint to which the head pressure is being
controlled.
Displays the position command being sent to the Control Valve. Displayed over the
range of 0.0% to 100%. The actual value of the output signal for a given error depends
on whether the PID Output Setpoint is set to direct or reverse. If set to direct, the 0.0%
output will be at minimum; the 100% output will be at maximum. If set to reverse, the
0.0% output will be at maximum; the 100% output will be at minimum.
Displays whether the Control Valve is in automatic or manual control.
Description
(15.0 to 60 PSID; default 23.0 PSID)
Sets the pressure differential to which the Control Valve will control the Head Pressure.
(0.0% to 100%; default 0.0%)
Sets the head pressure control valve minimum position to maintain adequate
condenser water flow to the chiller when running.
(0.0% to 100%; default 0.0%)
Sets the head pressure control valve to the position desired when the chiller is not
running.
(0 V to10 V, or 4 mA to 20 mA; default 0 V to 10 V)
Sets the output signal to the Control Valve to be in the form of either 0 to 10 VDC or 4
to 20mA.
(Direct or Reverse)
Allows the output signal to the Control Valve to be set to direct or reverse acting.
When set to direct, the voltage or current signal to the Control Valve is at minimum
for a 0% command and at maximum for a 100% command. When set to reverse, the
voltage or current signal to the Control Valve is at maximum for a 0% command and at
minimum for a 100% command.
(0.0% to 100%; default 0.0%)
Allows the Control Valve to be manually set to a pre-determined position between
0.0% and 100%.
Use to enter the Head Pressure Control PID variables below. Pressing this key places a
green box around the first changeable setpoint. Use the up/down, left/right arrows to
place the selection box around the desired setpoint. With the setpoint selected, press
the Enter key. A dialog box appears with the range of settings. Using the numeric keys,
enter desired value. Then, press the Enter key.
Sets the Proportional Gain of the Head Pressure Control (0.00 to 5.00; default 2.00).
Use the Change Setpoints key as described above to select/enter this setpoint.
Sets the Integral Gain of the Head Pressure Control (0.00 to 5.00; default 2.00). Use the
Change Setpoints key as described above to select/enter this setpoint.
Sets the Derivative Gain of the Head Pressure Control (0.00 to 5.00; default 0.00). Use
the Change Setpoints key as described above to select/enter this setpoint.
Description
Returns the user to Home screen.
Returns the user to Condenser screen.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center