York YK Style H Operation Manual page 49

Centrifugal liquid chillers with optiview control center
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

Table 28: Programmable
Field/LED name
Level Setpoint
Startup Position
Startup Delay
Ramp Time
Manual Increment
Open
Close
Set
High Threshold
Low Threshold
KP
Ti
Td
Table 29: Navigation
V09 software
Button
and earlier
Home
View
Condenser
View
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
Description
Displays the setpoint to which the refrigerant level is being controlled. (Adjustable 20
to 80%; default 50% requires Service Password).
Sets the starting position of the refrigerant valve to allow the system to match the load
quicker. (Adjustable 0 to 100%; default 50% requires Service password).
The amount of time the refrigerant level valve PID waits after start before it starts
controlling the valve position. This allows the system to stabilize before making valve
position changes (Set at 15 seconds but is adjustable with an Admin password).
After the chiller has been running for the level control startup delay time, if the
refrigerant level is less than the Level Setpoint, a linearly increasing ramp is applied
to the Level Setpoint. This ramp allows the level to go from the present level to the
programmed Level Setpoint over a period of time programmed as the Ramp Up Time.
This setpoint can only be changed with Admin level access (1 to 5 minutes; default 1).
This sets the percentage the refrigerant valve will manually be driven with each press
of the Open or Close buttons (0.1 to 10%; default 1.0%, requires Service password).
Pressing this button will set the Condenser Level Control Valve Mode to Manual
if it had been in Auto and will increase the current Condenser Level Control Valve
Command by an amount equal to the Manual Increment, with a maximum of 100.0%.
Pressing this button will set the Condenser Level Control Valve Mode to Manual if
it had been in Auto and will decrease the current Condenser Level Control Valve
Command by an amount equal to the Manual Increment, with a minimum of 0.0%.
Pressing this button will open a dialog box where the user can manually enter a valve
command. Once a legitimate value has been entered and the Enter key pressed, the
Condenser Level Control Valve Mode shall be set to Manual if it had been in Auto
and the Condenser Level Control Valve Command shall be set to the entered value.
(Adjustable 0.0% to 100.0%; default 50.0% Requires Service password)
Sets the high limit for the Subcooler Effectiveness Warning (Adjustable 0 to 100%;
default 50% requires Admin password).
Sets the low limit for the Subcooler Effectiveness Warning (Adjustable 0 to 100%;
default 50% requires Admin password).
Sets the Proportional value of the PID control loop. (Adjustable 0.1 to 15; default 1.0
requires Admin password).
Sets the Integral value of the PID control loop. (Adjustable 0.1 to 200; default 100
requires Admin password).
Sets the Derivative value of the PID control loop. (Adjustable 0.0 to 200; default 0.0
requires Admin password).
V10 and later
with YORK
Description
Chiller Access
Manager
View
Returns the user to Home screen.
View
Returns the user to Condenser screen.