Table 95: Display only fields
Field/LED name
Voltage Total Harmonic Distortion
(L1, L2, L3)
RMS Filter Current (L1, L2, L3)
Supply Current Total Demand
Distortion (L1, L2, L3)
RMS Supply Current (L1, L2, L3)
Note: For fields requiring access level of SERVICE. Service Technicians refer to the OptiView
Control Center - Service Instructions (Form 160.76-M1) for operation instructions and explanation
of all programmable setpoints and displayed values.
Table 96: Programmable
V09 software
Button
and earlier
Local Motor
Operator
Current Limit
Pulldown
Operator
Demand Limit
Pulldown
Operator
Demand Time
Table 97: Navigation
V09 software
Button
and earlier
Home
View
VSD
View
100
Description
Displays the 3-phase voltage Total Harmonic Distortion (THD) measurements.
Displays the 3-phase filter current values as measured by the Harmonic Filter.
Displays the 3-phase Current Total Demand Distortion (TDD) measurements.
Displays the 3-phase RMS Voltages across each line.
V10 and later
with YORK
Description
Chiller Access
Manager
Allows the user to specify the maximum allowed motor current (as a
percentage of FLA). When the motor current reaches this value, the pre-
Standard
rotation vanes will not be permitted to open further. If the motor current
rises above this value, the pre-rotation vanes will close to reduce the
current to this value.
Allows the user to specify the current limit value (as a percentage of FLA)
to which the chiller will be limited during the specified pulldown limit
Standard
time. This value will override the Motor Current Limit value during this
time period. This function is used to provide energy savings following
chiller startup.
Allows the user to set a period of time for which the pulldown demand
Standard
limit will be in effect after the chiller starts.
V10 and later
with YORK
Description
Chiller Access
Manager
View
Returns the user to Home screen.
View
Returns the user to VSD screen.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center