Table 98: Display only fields
Field/LED name
Date of Last Motor Lubrication
Warning or Fault
Date of Last Motor Lubrication
Time of Last Motor Lubrication
Operator Initials at Last Motor
Lubrication
Operating Hours Since Last Motor
Lubrication
Note: For fields requiring access level of SERVICE. Service Technicians refer to the OptiView
Control Center - Service Instructions (Form 160.76-M1) for operation instructions and explanation
of all programmable setpoints and displayed values.
Table 99: Programmable
V09 software
Button
and earlier
Lube Period
Service
Shutdowns
Service
Change Lube
Service
Type
102
Description
Displays the date of the last motor lubrication warning or safety shutdown.
Displays the date of the last motor lubrication. This parameter is automatically
recorded when the Operator enters their initials, name, or user ID using the Motor
Lube Acknowledge key.
Displays the time of the last motor lubrication. This parameter is automatically
recorded when the Operator enters their initials, name, or user ID using the Motor
Lube Acknowledge key.
Displays the initials, name or user ID entered by the Operator when the motor
lubrication is performed. Entered as a 3 to 8 character string using the Motor Lube
Acknowledge key.
Displays the run hours (in whole hours) accumulated since the last motor lubrication.
The value is reset to zero whenever the Operating hours (on the Operations screen) is
reset to zero or whenever the Operator enters their initials, name, or user ID using the
Motor Lube Acknowledge key.
V10 and later
with YORK
Description
Chiller Access
Manager
You can adjust the lube period over the range of 750 hours to 2,200
hours to match the motor lubrication requirement in Motor Relubrication
JCI Service
Instruction in Section 7 – Preventative Maintenance of Form 160.76-O1. Never
set this lube interval for more than 2,200 hours. A service password is
required.
If the Auto Lube Setpoint is set to Disabled, the Shutdown Setpoint is
used to enable or disable the safety shutdown that occurs if the operating
hours exceed the shutdown setpoint since last lubrication. The safety
JCI Service
shutdown can be enabled or disabled per the customer's preference. If
enabled, the safety shutdown will occur at the normal operating hours.
If disabled, a warning will be displayed but the safety shutdown will not
occur.
Allows the service technician to pick what lubricant type will be displayed
on the control panel from four commonly used lubricants or the default
JCI Service
See Motor Nameplate message if the specified lubricant is other than
one of the four common ones listed.