Table 111: Programmable
V09 software
Button
and earlier
Local Cooling
Operator
Setpoint
Leaving
Chilled Liquid
Temperature
Operator
Cycling Offset –
Shutdown
Leaving
Chilled Liquid
Temperature
Operator
Cycling Offset –
Restart
Local Motor
Operator
Current Limit
Pulldown
Operator
Demand Limit
Pulldown
Operator
Demand Time
Print
View
Table 112: Navigation
V09 software
Button
and earlier
Home
View
Setup
View
Remote Control Operator
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
V10 and later
with YORK
Description
Chiller Access
Manager
This value allows the user to define the Leaving Chilled Liquid
Temperature that is to be maintained by the chiller. It is programmable
over the range of 36.0°F to 72.0°F (2.2°C to 22.2°C) water or, 10.0°F to
Standard
72.0°F (-12.2°C to 22.2°C) brine.
Default = 45°F (7.22°C).
This value allows the user to specify the Leaving Chilled Liquid
Temperature at which the chiller will shut down on a LEAVING CHILLED
LIQUID – LOW TEMPERATURE cycling shutdown. This is done by defining
an offset below the Leaving Chilled Liquid Temperature Setpoint.
It is programmable over a range of 1°F to 70°F (-17.2 to 21.1) below the
Standard
setpoint, to a minimum cut-out of 34°F (1.11°C) water or, 6°F (-14.4°C)
brine. It establishes the minimum allowed temperature for the Leaving
Chilled Liquid Temperature and prevents over-cooling of the building.
Anytime the Leaving Chilled Liquid Temperature Setpoint is increased, the
shutdown temperature is increased by 0.1°F/second to allow the chiller
time to unload to the new setpoint.
This value allows the user to specify the Leaving Chilled Liquid
Temperature at which the chiller will restart after a shutdown on a
LEAVING CHILLED LIQUID – LOW TEMPERATURE cycling shutdown.
This is done by defining an offset above the Leaving Chilled Liquid
Standard
Temperature Setpoint. It is programmable over a range of 0°F to 37°F
above the setpoint, to a maximum restart value of 82°F.
The chiller will automatically restart when this temperature is reached.
This setpoint can be used to reduce chiller cycling by delaying the chiller
restart until the cooling load has increased.
Allows the user to specify the maximum allowed motor current (as a
percentage of FLA) when the chiller is running with Local Motor Current
control. When the motor current reaches this value, the pre-rotation
Standard
vanes will not be permitted to open further.
If the motor current rises above this value, the pre-rotation vanes will
close to reduce the current to this value.
Allows the user to specify the current limit value (as a percentage of
Full Load Amps) to which the chiller will be limited during the specified
pulldown limit time. This value will override the Motor Current Limit value
Standard
during this time period. This function is used to provide energy savings
following chiller start-up. Pulldown demand limit is ignored in BAS control
source because the BAS system is expected to use its algorithms to reset
current limit as required in that operating mode.
Allows the user to set a period of time for which the pulldown demand
Standard
limit will be in effect after the chiller starts.
View
Generates the setpoints print report.
V10 and later
with YORK
Description
Chiller Access
Manager
View
Returns the user to Home screen.
View
Navigates to the subscreen allowing setup of general system parameters.
Navigates to the subscreen allowing setup of the Remote Control BAS
Standard
interface.
115