York YK Style H Operation Manual page 117

Centrifugal liquid chillers with optiview control center
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

Table 114: Programmable
V09 software
Button
and earlier
Select Run/Stop Operator
Select Cooling
Operator
Select Current
Operator
Limit
Table 115: Navigation
V09 software
Button
and earlier
Home
View
Setpoints
View
Operations
View
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
V10 and later
with YORK
Description
Chiller Access
Manager
Allows the user to select the Control Source for Run/Stop (Local, BAS or
Standard
Hardwire).
Allows the user to select the Control Source for Cooling. (Local, BAS, 0 VDC
to 10 VDC, 4 mA to 20 mA, or PWM) and also set the remote analog signal
minimum and maximum value setpoints. The remote analog signal can
Standard
adjust the setpoint between the user selected Maximum (max signal) and
the user selected Minimum (min signal). Refer to Form 160.76-PW4 for
more details on the BAS interfaces.
Allows the user to select the Control Source for Current Limiting. (Local,
BAS, 0 VDC to 10 VDC, 4 mA to 20 mA, or PWM). The remote analog signal
Standard
can adjust the setpoint between 30% (max signal) and 100% (min signal).
Refer to Form 160.76-PW4 for more details on the BAS interfaces.
V10 and later
with YORK
Description
Chiller Access
Manager
View
Returns the user to Home screen.
View
Navigates to the Setpoints Screen.
View
Navigates to the Operations Screen.