York YK Style H Operation Manual page 37

Centrifugal liquid chillers with optiview control center
Hide thumbs Also See for YK Style H:
Table of Contents

Advertisement

Table 15: Display only fields
Field/LED name
Heating Condenser Liquid Flow
Switch (LED)
Condenser Liquid Flow Switch (LED)
Drop Leg Refrigerant Temp
Subcooling Temperature
High Pressure Switch (Open /
Closed)
Condenser Liquid Flow Switch
Condenser Liquid Pump (Run / Stop) Indicates whether condenser liquid pump is operating.
Condenser Refrigerant Level
Active Level Setpoint
Level Control Valve Command
Note: For fields requiring access level of SERVICE, Service Technicians must refer to the
OptiView Control Center - Service Instructions (Form 160.76-M1) for operation instructions and
explanation of all programmable setpoints and displayed values.
Table 16: Programmable
V09 software
Button
and earlier
High Pressure
Warning
Service
Threshold
Drop Leg
(Enabled/
Service
Disabled)
Fault
Service
Acknowledge
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
Description
Displays the status of the flow switch in the heating condenser tube bundle.
Illuminates when liquid flow is present. Otherwise, it is extinguished. Only appears
when the Heat Recovery is enabled.
Displays the status of the flow switch in the standard condenser tube bundle.
Illuminates when liquid flow is present. Otherwise, it is extinguished. Only appears
when the Heat Recovery is enabled.
Displays the temperature of the refrigerant in the drop leg between the condenser
and evaporator shells, if the sensor is present.
Displays the difference between the Condenser Refrigerant temperature and the
Drop Leg Refrigerant temperature. The Condenser Refrigerant temperature will be
represented by the Condenser Saturation temperature. If the Drop Leg Sensor is not
present, this temperature is not displayed.
Displays the present position of the high pressure switch. This will indicate whether a
high pressure fault is present.
Indicates whether flow is present in the condenser.
Displays the present position of the refrigerant level if this function is enabled.
Displays the setpoint to which the refrigerant level is being controlled.
Displays the value of the refrigerant valve position command.
V10 and later
with YORK
Description
Chiller Access
Manager
This value allows the user to define the condenser pressure at which the
chiller initiates a warning.
JCI Service
When Heat Pump Duty is set to enabled, this setpoint is automatically set
to 193 PSIG.
When a Drop Leg Refrigerant Sensor has been installed, it must be
JCI Service
enabled via this toggle before the system can use the new, enhanced
resolution input.
This allows clearing of the High Condenser Pressure Fault while Shutdown
JCI Service
(Condenser-High Pressure Stopped).
37