3. Perform the First Start
The motor is now ready to run.
Press START/STOP button to start the motor.
To set the output frequency in local control, press ENTER. Pressing the
UP/DOWN buttons changes the output immediately. Press ENTER to
return to OUTPUT display.
To stop the drive press START/STOP button.
4. Check Rotation Direction
Check that the motor is running in the correct direction.
To change the rotation direction of the motor disconnect the mains power
from the ACS 160 and wait 5 minutes for the intermediate circuit
capacitors to discharge. Verify that the power is off.
Exchange the position of any two motor cable phase conductors at the
motor terminals or at the motor connection box.
Apply the mains power and start the drive.
Rotation can also be
REVERSE button (parameter 1003 must be set to
5. Connect the I/O Control Signals
Disconnect the mains supply of the ACS 160, and wait 5 minutes for the intermediate circuit
capacitors to discharge.
Note! The unit is delivered with Factory macro 0 pre-set.
For the following instructions Factory macro 0 is selected, for all other macros refer to the section
on Application Macros.
For analogue speed reference connect potentiometer (2-10 k
Default setting for AI 1 is voltage.
Default motor nominal values are: 400 V, 50 Hz and 1440 rpm for unit types ACS 163-xKx-3-A, -B,
-D, -E. 460 V and 60 Hz and 1750 rpm for ACS 163-xKx-3-R, -S, -U, -V type units.