ABB ACS 160 User Manual page 131

Driveit low voltage ac drives
Table of Contents

Advertisement

Recommended
Symmetrical shielded cable: three phase
conductors and a concentric or otherwise
symmetrically constructed PE conductor,
and a shield
PE
conductor
and shield
Not allowed for motor cables.
A four -conductor system: three phase
conductors and a protective conductor.
PE
Figure 33 Cable recommendations and restrictions.
The general rule for cable screen effectiveness is: the better and tighter the screen of the cable, the
lower the radiated emission level. Example of an effective construction is presented in Figure 34.
Insulation jacket
Figure 34 Effective motor cable screen (e.g. Ölflex-Servo-FD 780 CP, Lappkabel or MCCMK, NK
Cables).
Clamp the cable shield into the gland plate at the converter end and twist the cable screen wires
together into a bundle not longer than five times its width and connect it to the terminal marked
if you are using cable without a separate PE conductor.
At the motor end the motor cable screen must be earthed 360 degrees with an EMC cable gland
(e.g. ZEMREX SCG Screened cable glands) or the screen wires must be twisted together into a
bundle not longer than five times its width and connected to the PE terminal of the motor.
ACS 160 User's Manual
Shield
PE
Braided metallic screen
Allowed
A separate PE conductor is required if the
conductivity of the cable shield is < 50 %
of the conductivity of the phase conductor.
Shield
Allowed for motor cables with phase
conductor cross section up to 10 mm
Inner insulator
L2
L3
Shield
PE
2
.
L1
121
,