Table 9 Faults.
Fault Code
1
OVERCURRENT
2
DC OVERVOLTAGE
3
160
ACS
4 **
SHORT CIRCUIT
5
OUTPUT OVERLOAD
6
DC UNDERVOLTAGE
7
ANALOGUE INPUT
8
ANALOGUE INPUT
9
MOTOR OVERTEMP
10
PANEL LOSS
11
PARAMETERING
12
MOTOR STALL
13
SERIAL COMM LOSS
14
EXTERNAL FAULT SIGNAL
15 **
OUTPUT EARTH FAULT
16 **
DC BUS RIPPLE
110
Name
Description
Output current is excessive.
Intermediate circuit DC voltage is excessive.
ACS 160 heat sink temperature is excessive. Temperature trip limit is
OVERTEMP
105 °C.
Fault current. Possible reasons for this fault are:
Inverter overload condition. The ACS 160 output current exceeds the
ratings given in Reference Section P.
Intermediate circuit DC voltage is not sufficient.
1
Analogue input 1 loss. Analogue input value is less than
(1301). See also parameter 3001
2
Analogue input 2 loss. Analogue input value is less than
(1306). See also parameter 3001
Motor overtemperature condition as estimated by the ACS 160. Refer to
parameters 3004 – 3008.
Panel communication loss. Control panel is disconnected when the
drive is receiving start, stop and direction commands from the panel.
- Drive is in local control mode (LOC is shown in the control panel
display), or
- Drive is in remote control mode (REM is shown) and is parameterised
to accept start/stop, direction or reference from the panel. Refer to
parameters in groups 10 COMMAND INPUTS and 11 REFERENCE
SELECT.
See also parameter 3002
Parameter values are inconsistent:
Motor stall. This may be caused by excessive load or insufficient motor
power. Refer to parameters 3009 – 3012.
Serial communication through Standard Modbus Channel is lost.
External fault is active. See parameter 3003
Earth fault. The load on the incoming mains system is out of balance.
Motor load may be too high
Acceleration time may be too short (parameters 2201
1 and 2203
TIME
ACCELER TIME
Motor or motor cable is faulty or connected wrong.
Check mains for static or transient overvoltages
Deceleration time may be too short (parameters 2202
1 and 2204
TIME
DECELER TIME
Brake chopper (if present) may be underdimensioned
Check air flow and fan operation.
Check motor power against unit power.
There is a short-circuit in the motor cable(s) or motor
Supply disturbances
Mains phase may be missing
Fuse may be blown
PANEL LOSS
1 >
MINIMUM AI
MAXIMUM AI
2 >
MINIMUM AI
MAXIMUM AI
>
MINIMUM FREQ
MAXIMUM FREQ
Check connections between external control system and the
ACS 160.
Refer to parameters 5204
.
FUNC
There may be a fault in the motor or motor cable.
Motor cable may be too long.
Ripple voltages on the DC bus are too large.
Mains phase may be missing
Fuse may be blown
2).
2)
<
.
AI
MIN FUNCTION
<
.
AI
MIN FUNCTION
.
1 (parameters 1301, 1302)
2 (parameters 1304, 1305)
(parameters 2007, 2008)
and 5205
COMM FAULT TIME
EXTERNAL FAULT
ACS 160 User's Manual
ACCELER
DECELER
1
MINIMUM AI
2
MINIMUM AI
COMM FAULT
.