ABB ACS 160 User Manual page 133

Driveit low voltage ac drives
Table of Contents

Advertisement

Wall Mounted Units
Compliance with EN61800-3 EMC Standard
Second Environment
Use a converter type which complies with the 2nd environment EMC requirements as specified in
Table 10 and follow the instructions for all cable screen connections.
The motor cable lengths have to be limited as specified in Table 10 and must have effective screen
according to Figure 34. At the motor end, the cable screen must be earthed 360 degrees with an
EMC cable gland (e.g. Zemrex SCG screened cable glands).
Table 10 Maximum motor cable lengths (m / ft) to comply with EN 61800-3 2nd Environment
Wall mounting with
EMC filter
2nd Environment
Type
ACS 163-1K1-3-E /-V
ACS 163-1K6-3-E /-V
ACS 163-2K1-3-E /-V
ACS 163-2K7-3-E
ACS 163-4K1-3-E /-V 100 /328
First Environment
Use a converter type which complies with the 1st environment EMC requirements as specified in
Table 11 and follow the instructions for all cable screen connections.
The motor cable lengths have to be limited as specified in Table 11 and must have effective screen
according to Figure 34. At the motor end, the cable screen must be earthed 360 degrees with an
EMC cable gland (e.g. Zemrex SCG screened cable glands).
Table 11 Maximum cable lengths (m / ft) to comply with EN 61800-3 1st Environment
Wall mounting with
EMC filter
1st Environment
Type
ACS 163-1K1-3-E /-V
ACS 163-1K6-3-E /-V
ACS 163-2K1-3-E /-V
ACS 163-2K7-3-E
ACS 163-4K1-3-E /-V
ACS 160 User's Manual
Restricted Distribution
400 V
4 kHz
8 kHz
m / ft
m / ft
40 / 131
20 / 66
20 / 66
60 / 197
20 / 66
20 / 66
80 / 262
20 / 66
20 / 66
90 / 295
50 / 164
40 / 131
100 / 328
80 / 262 80 / 262 100 / 328 100 / 328
Restricted Distribution
400 V
4 kHz
8 kHz
4 kHz
m / ft
m / ft
m / ft
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
10 / 33
Input voltage
Switching frequency
480 V
4 kHz
8 kHz
4 kHz
m / ft
m / ft
m / ft
10 / 33
40 / 131
10 / 33
60 / 197
10 / 33
80 / 262
30 / 98
90 / 295
Input voltage
Switching frequency
480 V
8 kHz
4 kHz
m / ft
m / ft
10 / 33
5 / 16
10 / 33
5 / 16
10 / 33
5 / 16
10 / 33
5 / 16
10 / 33
5 / 16
Unrestricted Distribution
480 V
400 V
8 kHz
4 kHz
m / tf
m / ft
20 / 66
20 / 66
20 / 66
20 / 66
20 / 66
20 / 66
50 / 164
40 / 131
80 / 262
Unrestricted Distribution
480 V
400 V
8 kHz
4 kHz
m / ft
m / ft
5 / 16
5 / 16
5 / 16
5 / 16
5 / 16
5 / 16
5 / 16
5 / 16
5 / 16
5 / 16
8 kHz
m / ft
10 / 33
10 / 33
10 / 33
30 / 98
80 / 262
8 kHz
m / ft
5 / 16
5 / 16
5 / 16
5 / 16
5 / 16
123

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents