System Water Characteristics; System Water Load - Ravelli HR EVO 200 SMART Use And Maintenance Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 124
EN
Rev.1 08/09/2021
Pag.36
Diagram 3 (boiler sensor + buffer tank sensor)
Diagram 3 is to be used in a system where both a water buffer tank for the heating system and a DHW boiler are present.
The operating logic is similar to that of Diagram 1. Also in this type of circuit, the boiler water temperature is managed by the appliance
and room temperature by a control unit (not supplied) that controls the buffer tank and any zone valves. The buffer tank temperature
is controlled by the appliance through a sensor.
LEGEND
Stufa a Pellet
1- Pellet stove / boiler
2- Distribution manifolds
3- Radiators
4- Thermometer
5- Pressure gauge
6- Anti-condensation valve
The diagram shown here is indicative and may not display all the components required to properly operate the system. Rely on a
qualified thermal technician for the hydraulic system design.

System water characteristics

The chemical-physical characteristics of the system and replenishing water are important for the proper operation and service life of
the appliance; in fact, with the use of low quality water the most frequent problem is due to scale, which causes a reduction in heat
exchange and generates corrosion.
Therefore, we invite you to check the quality and hardness of the water with your supplier.
We recommend the installation of a softener (limescale filter) in correspondence with the system loading. This precaution becomes
essential in the conditions listed below:
medium and high water hardness (> 15 ° f)
considerable quantities of make-up water or subsequent fillings
plants of a certain complexity and size.
National and local laws may require the use of water softening systems. The technician responsible for the plumbing
installation is invited to check what is reported in the regulations in force.

System water load

Once the plumbing connections have been completed, the appliance and its system can be loaded.
To facilitate the escape of air, unscrew the cap of the automatic vent valve (Jolly valve) of the appliance and open the vent valves in
the system. Bleed the air even after the first hours of operation and, if necessary, also periodically (for example in the event of noises
and gurgling).
The filling pressure of the COLD system must be 1 bar (100 kPa). In order to ensure correct operation of the appliance, the HOT
pressure must be approximately 1.5 bar (150 kPa).
If during operation the system pressure drops to values below the minimum indicated above, the user must bring it back to the initial
value by acting on the filling tap.
It is possible to load the system and keep it at the correct pressure also by means of a special automatic filling unit.
Periodically check the system water pressure, using the appropriate function on the display.
Use and maintenance manual HR EVO Smart
7- Check valve
8- Group of direct distribution
9- Thermostatic distribution unit
10- Radiant panel (underfloor heating)
11- Shut-off valve
12- Thermostat
13- Expansion vessel (tank)
14- Pump station for solar thermal system
15- Solar thermal collector
16- Thermostatic mixing valve
17- Booster pump
18- Buffer tank
19- Motorised three-way valve with spring return
20- Gas boiler
21- Power separation system
22- Motorised three-way valve
23- DHW storage
24- Flow switch

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hr evo 250 smart

Table of Contents