Other Handling Systems - Ravelli HR EVO 200 SMART Use And Maintenance Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 124

Other handling systems

The boiler must be handled carefully, avoiding any bumping, always keeping it upright for transport and only using forklifts; alterna-
tively, it can be moved using lifting straps connected to the appropriate hooks.
Make sure the equipment used for lifting and transport can take the boiler's weight, specified on the data plate and in this manual.
Place of installation, positioning
Place the boiler in the required location, making sure it is possible to operate and service the unit in any position needed to do the
work.
Check that the room where the appliance is installed has the upper, side and rear spaces required for maintenance and cleaning of
the appliance, the flue gas ducts and the flue pipe.
Also check that the pellet hopper is easily accessible for fuel loading.
The minimum distances for maintenance and safety must comply with the following table:
Minimum maintenance distances
R Right side
500 mm
L Left side
500 mm
B Rear
500 mm
A Front
1000 mm
Minimum height of
2,3 m
the installation room
The unit is suitable for operation in technical environments with min. temperature not below 0°C; it comes complete with an antifreeze
function that activates the heating pump for system water temperatures below 6°C, safeguarding: heating chamber, heating/DHW
circuit. The antifreeze function is active only when the boiler is electrically powered.
Use and maintenance manual HR EVO Smart
2 eyebolt M10 (not provided)
L
Optional tank
Rev.1 08/09/2021
Pag.27
B
R
Boiler
A
EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hr evo 250 smart

Table of Contents