Performance specifications

10.1
General
10.1.1 Reference conditions
Measurement target: Stationary metal plate, no disturbing objects
Temperature: 59 to 77 °F (15 to 25 °C)
Ambient pressure: 14 to 15 psi (960 to1060 mbar)
Relative humidity: 25-75%
Damping: Default value, 0 s
10.1.2 Instrument accuracy (under reference conditions)
Range < 130 ft. (40 m)
Range > 130 ft. (40 m)
10.1.3 Measuring range
10 to 262 ft. (3 to 80 m)
10.1.4 Repeatability
±0.04 in. (±1 mm)
10.1.5 Ambient temperature effect
±0.04 in. (±1 mm)/10 K
10.1.6 Sensor update rate
Measuring rate
10 Hz
Burst rate
5 Hz (or configurable 2 to 10 Hz)
10.1.7 Beam width
4.5°
(3)
Refers to inaccuracy according to IEC 60770-1 when excluding installation
dependent offset. See the IEC 60770-1 standard for a definition of radar specific
performance parameters and if applicable corresponding test procedures.
(4)
Ambient temperature effect specification valid over temperature range -40 °F to 176
°F (-40 °C to 80 °C).