WIKA GDM-63 Operating Instructions Manual page 20

Gas density monitor
Table of Contents

Advertisement

Available languages

Available languages

9. Specifications
Specifications
Case
Window
EN
Ring
Permissible air humidity
Ingress protection
Weight
With gas filling
With fill fluid
High-voltage test 100 %
Electrical connection
Number of switch contacts
Switching directions
Switching functions
Circuits
Switching accuracy
Switch point = calibration
pressure P
E
Switch point ≠ calibration
pressure P
E
Max. switching voltage
Switching power
Material of switch contacts
For further specifications, see the order documentation.
20
Stainless steel, with gas filling
Stainless steel, with filling liquid
Gas-tight: Leakage rate ≤ 1 · 10
Laminated safety glass or clear non-splintering plastic
Bayonet ring, stainless steel, secured by means of 3 welding
spots
≤ 90 % r. h. (non-condensing)
IP65 per IEC60529
Approx. 0.8 kg
Approx. 1.2 kg
2 kV, 50 Hz, 1 s
Cable outlet, length 1 m
Cable bushing from glass
1 or 2 magnetic snap-action contacts
Falling pressure or rising pressure
Normally open, normally closed or change-over contact
Galvanically connected (not for change-over contact) or
galvanically isolated
See accuracy specifications
Parallel to the reference isochore of the calibration pressure
AC 250 V
With gas filling: 30 W / 50 VA, max. 1 A
With fill fluid: 20 W / 20 VA, max. 1 A
80 % Ag / 20 % Ni, gold-plated
WIKA operating instructions gas density monitor model GDM-63
mbar · l / s
-5

Advertisement

Chapters

Table of Contents
loading

Table of Contents