10. Select Installer and enter the installer code.
11. Go to the Configuration tab and give the unit a logical name. For example, MCU Primary. Do the same for the Replica units.
It's good practice to label them Replica 1, Replica 2 etc.
Note: battery settings must be configured the same on all units.
12. Return to the Configuration tab of the Primary unit. All settings are done here. However, if Mastervolt Lithium-Ion batteries
are connected, all events, like Stop Discharge for example, must be configured for ALL units separately.
13. From the Cluster drop-down list, select Single Phase. You may need to maximize the MasterAdjust window or scroll all the
way to the right to see this.
14. From the Dev. Per phase drop-down list, select the number of units in parallel (Primary + Replica).
15. Click the Select devices button to be able to select the Replica unit(s).
Mass Combi Ultra, Mass Combi Pro – Installation Manual Multiple Units
Parallel configuration with MasterAdjust