Ventilation
LGH-RVX
TOTAL HEAT EXHANGE VENTILATION SYSTEM
230V
I.M.
(see tab.)
Installation Data*
MODEL
Section A
LGH-RVX
2x1,5 +T
Pay attention
1. It is not possible to connect the PZ-61DR-E remote control (connection "B") or an external ON-OFF switch (connection "D") simultaneously with the
Lossnay operating interlock to a Mr. Slim unit ( connection "C");
2. The simultaneous connection of the PZ-61DR-E remote control and an external ON-OFF switch is possible;
3. To interlock the Lossnay operation to a Mr. Slim A control (connection "C") it is necessary to configure the specific function on the latter (see following
pages). The connector for connecting to the Mr. Slim unit is supplied with the Lossnay.
4. Shielded cable maximum length 200 m.
Conditions of the Mr. SLIM series compatible with the Lossnay ventilation system
TYPE
4 way cassette
Ducted
* Horizontal installation only.
76
TM1
A
L
TM4
N
B
Breaker
10 A
MODEL
PLA-BA / SLZ-KA
PEAD-JA / PEA-GA /SEZ-KD
TM2
clean contact
1
2
PZ-61DR-E
Connection B
Section
Max Lenght
Section
2x1
500 m
TYPE
Ceiling
Wall mounted
Floor standing
C
1
CN2L
2
3
D
PLA-RP
Connection C
Connection D
Max Lenght
Section
2x1
500 m
2x1
MODEL
PCA-KA / HA
PKA-HA / KA
PSA-KA
Max Lenght
500 m