MITSUBISHI ELECTRIC / FUNCTION AND SETTINGS
A CONTROL
- MR.SLIM - ROTATION E BACKUP
Special functions PAR-40MAA / PAR-21MAA
Rotation, Back-Up e 2nd stage
Outdoor unit 1
Indoor unit 1
PAR40MAA
Setting mode for functions: ROTATION, BACK-UP E SET UP 2nd Stage
Rotation and Back-up
Setting No.
(Request code)
No.1 (310)
Monitoring the request code of current setting
Rotation and Back-up OFF
No.2 (311)
(Normal group control operation)
No.3 (312)
Back-up function only
Rotation ON
No.4 (313)
(Alternating interval = 1day) and back-up function
Rotation ON
No.5 (314)
(Alternating interval = 3days) and back-up function
Rotation ON
No.6 (315)
(Alternating interval = 5days) and back-up function
Rotation ON
No.7 (316)
(Alternating interval = 7days) and back-up function
Rotation ON
No.8 (317)
(Alternating interval = 14days) and back-up function
Rotation ON
No.9 (318)
(Alternating interval = 21days) and back-up function
114
Outdoor unit 2
Indoor unit 2
Setting contents
SETTING OF OUTDOOR UNIT REFRIGERANT ADDRESS
Main and sub units should be set using Dip-Switch SW1 (da
3 a 6) on the outdoor unit PC board (standard set is Off). Set
refrigerant address as follow:
Refrigerant
address
00
OC-1
Main
unit
IC-1
Refrigerant address SW1 have to be setted on
Refrigerant address 00
SW1
ON
1
2
3
OC-1
Initial
Setting No.
settings
(Request code)
No.1 (320)
No.2 (321)
No.3 (322)
No.4 (323)
No.5 (324)
Refrigerant
address
01
OC-2
Sub
3/2
3/2
unit
IC-2
the outdoor unit
Refrigerant address 01
SW1
ON
4
5
6
1
2
3
4
5
OC-2
2nd Stage
Setting contents
Monitoring the request code of current setting
Cut-in function OFF
Cut-in function ON (Set point = Set temp.+ 4: [7.2°F]
Cut-in function ON (Set point = Set temp.+ 6: [10.8°F]
Cut-in function ON (Set point = Set temp.+ 8: [14.4°F]
LEGENDA
OC = Outdoor unit
IC =
RC = Remote
controller
6
Initial
settings