MSY-TP
M SERIES - WALL-MOUNTED - Cooling only
230V
Breaker
DIAMETER
SIZE
Liquid mm
Gas mm
(inches)
(inches)
35
6,35 (1/4")
9,52 (3/8")
50
6,35 (1/4")
9,52 (3/8")
MFZ-KT
M SERIES - FLOOR STANDING - DC Inverter/Heat Pump
230V
Breaker
DIAMETER
SIZE
Liquid mm
Gas mm
(inches)
(inches)
25
6,35 (1/4")
9,52 (3/8")
35
6,35 (1/4")
9,52 (3/8")
50
6,35 (1/4")
12,7 (1/2")
L
N
MUY-TP_VF
EXTERNAL PIPING
Max
Max
Max
Precharge
Height
Lenght
Pipe Bends
12
20
10
0,85
12
20
10
0,85
L
N
SUZ-M_VA
EXTERNAL PIPING
Max
Max
Max
Precharge
Height
Lenght
Pipe Bends
12
20
10
0,65
12
20
10
0,90
30
30
10
1,20
S1
S2
S3
REFRIGERANT CHARGE
Precharge
Additional
lenght
charge
Kg
mt.
g/mt
7
20
S1
S2
S3
REFRIGERANT CHARGE
Precharge
Additional
lenght
charge
Kg
mt.
g/mt
7
20
MITSUBISHI ELECTRIC / M SERIES
S1
S2
S3
MSY-TP_VF
ELECTRICAL DATA
Operating
tonCO
eq
tonCO
eq
current
2
2
precharge
max charge*
max
0,57
0,75
9,6 A
0,57
0,75
9,6 A
S1
S2
S3
MFZ-KT_VG
ELECTRICAL DATA
Operating
tonCO
eq
tonCO
eq
current
2
2
precharge
max charge*
max
0,44
0,61
7,0 A
0,61
0,78
8,7 A
0,81
1,12
14,0 A
Breaker
10 A
10 A
Breaker
10 A
10 A
20 A
13

Advertisement

loading