Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
24.4
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B4.
"A"
"A"
Rev: 1

Re-enable zone (H2/B4)

Disabled zones are listed in menu H4/U1 from which it is also
possible to get a print-out.
Re-enabling via this menu has higher priority than automatic re-
enabling.
When all zones have been re-enabled, The LED "Disablements" (L8)
will be turned OFF, if there are no other disablements in the system.
NOTE! It is not possible to collectively re-enable a number of alarm
points (zone-address) that are individually disabled via menu H2/B2.
Text in display
Disable or re-enable
Disable zone
Re-enable zone
Re-enable zone: 000
Re-enable zone
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B4
ACCEPT?
ACCEPT? B4
80
Comments
According to chapter
"Access", see page 72.
If there are no zones to re-
enable, menu B4 will be
L
shown again.
L=a list in which you can
scroll.
If it's the correct zone to
re-enable, press "A" to
accept. If not, scroll or
write the wanted zone and
press "A" to accept.
If more re-enablements
shall be done, continue like
above. If not, scroll or
press "Return" to menu
H2. Scroll or press
"Return" to log off.