Display current consumption in unit
(H5/A5)
The resolution is not very high, i.e. the displayed values give only a
rough idea of the current consumption.
Control unit: The total current consumption (including the charging
current at 24V) for the selected control unit (c.i.e.) when it is
connected to the mains (230 V AC), i.e. this function is not working
by battery backup.
Charging: The battery charging current for the selected control unit
(c.i.e.). This is at 24 V, i.e. before the DC/DC converter for battery
charging voltage etc.
NOTE!
Control unit current >3800 mA is presented as >3800
mA.
Charging current <100 mA can not be correctly
presented.
The displayed "Charging" value (
multiplied by two when "High current charging mode"
has been selected via jumper "JP2" on the Charger board
1657. (JP2 shunted = High current charging mode.)
Text in display
Display current consumption in unit
From which control unit shall current
consumption be displayed: 00
Wait......
No reply from control unit.....
Current consumption control unit 00
Control unit:
xxxx mA Charging: xxxx mA
Display current consumption in unit
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? A5
ACCEPT?
ACCEPT? A5
109
) shall be
xxxx mA
Comments
According to chapter
"Access code for service
(H5)", see page 104.
Write control unit number.
Press "A" to accept.
If the control unit don't
exist or don't answer, this
message will be shown.
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.