WIRING INSTRUCTIONS

■ TIGHTENING TORQUE
Separable screw terminal wiring screw: 0.5 N·m
Separable screw terminal fixing screw: 0.5 N·m
■ SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.25 to 0.75 mm
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.
3 (.12) max.
12 (.47) max.
■ HOW TO REMOVE SEPARABLE SCREW TERMINAL
The terminal block is separable in two pieces. Evenly loos-
en two screws on top and bottom of the terminal block to
separate.
FUNCTIONS
■ OUTPUT AT THE LOSS OF COMMUNICATION
• Output Hold
If the network module is in error, the module holds the
signal at error and stands by until the communication re-
covers.
• Output set value
If the network module is in error, the module holds the
signal at error or power up and stands by until the com-
munication recovers. The signal at error or power up is se-
lectable with PC configurator software (Model: R30CFG).
Not depending on output at the loss of communication set-
ting, when power up the module holds the signal at error or
power up and stands by until the normal data is received.
2
3.2 (.13) dia.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
PC CONFIGURATOR
The following parameter items can be set with using PC
Configurator Software (model: R30CFG).
Refer to the users manual for the R30CFG for detailed op-
eration of the software program.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
SETTING RANGE
Unused setting
CH enabled
CH disabled
Output range
-10 – +10 V DC
-5 – +5 V DC
0 – 10 V DC
0 – 5 V DC
1 – 5 V DC
Fine zero adjustment
-320.00 – +320.00 (%)
Fine gain adjustment
-3.2000 – +3.2000
Scaled range zero
-32 000 – +32 000
Scaled range span
-32 000 – +32 000
Output range at
-15.00 – +115.00 (%)
communication
failure or power up
■ CHANNEL BATCH SETTING
PARAMETER
SETTING RANGE
Simulate output
Normal output
Simulation data
Output at the loss
Hold the output data
of communication
User set data output
R30YV4
DEFAULT
SETTING
CH enabled
-10 – +10 V DC
0.00 (%)
1.0000
0
10 000
-15.00 (%)
DEFAULT
SETTING
Normal output
Hold the out-
put data
EM-9005 Rev.2 P. 5 / 5