■ CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE
terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.
*
1
COM
2
X0
3
X2
4
X4
5
X6
6
X8
*
7
X10
8
X12
9
X14
10
COM
11
X1
12
X3
13
3
X5
FE
14
6
X7
24V DC
15
7
X9
0V
16
X11
17
X13
18
X15
19
V
20
Y16
21
Y18
22
Y20
23
Y22
24
Y24
25
Y26
26
Y28
27
Y30
28
V+
29
Y17
30
Y19
31
Y21
32
Y23
33
Y25
34
Y27
35
Y29
36
Y31
*MECHATROLINK connectors are internally connected.
The network cable can be connected to either one.
Input Connection Examples
PNP Connection
+
1
COM
10
COM
2
X0
18
X15
NPN Connection
+
1
COM
10
COM
2
X0
18
X15
Output Connection Examples
+ −
28
V+
19
V-
20
Y0
36
Y15
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp

MOUNTING REQUIREMENTS

220 (8.66)
2–M4

WIRING INSTRUCTIONS

■ TORQUE
Wiring screw for separable terminal: 0.5 N∙m
Fixing screw for separable terminal: 0.5 N∙m
■ SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd, Nichifu Co., Ltd
3.3 (.13) max
■ HOW TO UNMOUNT THE SEPARABLE TERMINAL
The separable terminal of the unit is 2 piece constructions.
It is possible to remove the terminal by loosening two screws
of terminal alternately.
R7K4FML3-6-DAC32B
unit: mm (inch)
(AWG 22 to 16)
2
mm (inch)
EM-7773-E Rev.3 P. 5 / 11