Download Print this page
M-system R30CT4E Instruction Manual

M-system R30CT4E Instruction Manual

Ac current input module

Advertisement

Quick Links

INSTRUCTION MANUAL
AC CURRENT INPUT MODULE
(4 points, isolated, clamp-on current sensor type CLSE use)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
AC current input module ....................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ GENERAL PRECAUTIONS
• Before you remove the terminal block or mount it, turn off
input signals for safety.
■ HOT INSERTION/REMOVAL OF MODULES
• It is possible to replace the module with the power sup-
plied, provided that modules are of the same model num-
ber and that the same Installation Base slot is used.
• Turn off input signals before replacing the module for
safety. Note that replacing multiple modules at once may
greatly change line voltage levels. We recommend that
you replace them one by one.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 10 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
• Be sure to attach the terminal cover for safety.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
R30CT4E
EM-9018 Rev.1 P. 1 / 5

Advertisement

loading

Summary of Contents for M-system R30CT4E

  • Page 1 (4 points, isolated, clamp-on current sensor type CLSE use) BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ CONFORMITY WITH EU DIRECTIVES contents of the package you received as outlined below. • The equipment must be mounted inside the instrument If you have any problems or questions with the product, panel of a metal enclosure.
  • Page 2: Component Identification

    No connection Input K3 No connection Input L3 No connection Input K4 No connection Input L4 No connection No connection No connection EM-9018 Rev.1 P. 2 / 5 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3: Installation

    Lock Tab 3) Tighten the base fixing screw using a screwdriver (stem length: 70 mm/2.76” or more) (torque 0.5 N·m). Base Fixing Screw EM-9018 Rev.1 P. 3 / 5 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: Terminal Connections

    ■ CONNECTION DIAGRAM SOURCE INTERNAL BUS INPUT 1 LOAD INTERNAL POWER SOURCE INPUT 2 LOAD SOURCE INPUT 3 LOAD SOURCE INPUT 4 LOAD EM-9018 Rev.1 P. 4 / 5 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 5: Wiring Instructions

    20 ms 10 ms Operational delay at 0.0 – 60.0 sec. 5.0 sec. power ON Simulate input Normal input Normal input Simulated data EM-9018 Rev.1 P. 5 / 5 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...