Download Print this page

M-system R3-NC1 Instruction Manual

Cc-link interface module

Advertisement

Quick Links

INSTRUCTION MANUAL
CC-Link INTERFACE MODULE
(CC-Link Ver.1.10; for 16-point analog signals)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Network interface module ..................................................(1)
Terminating resistor (110 Ω, 0.5 W) ...................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■ HOT SWAPPABLE MODULES
• The module can be replaced while the power is ON. Be
sure to replace it when the module is not communicat-
ing with a host, as it may affect the system. Replacing
multiple modules at once may greatly change line voltage
levels. We highly recommend to replace them one by one.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 120V AC rating: 85 – 132V, 47 – 66 Hz, approx. 20VA
200 – 240V AC rating: 170 – 264V, 47 – 66 Hz, approx. 20VA
24V DC rating: 24V ±10%, approx. 12W
■ GENERAL PRECAUTIONS
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base Model R3-BS, or Model R3-BSW
for free I/O address capability.
Before mounting the Network Interface Module onto the
Base, be sure to configure the module as explained below.
■ DATA ALLOCATION
The setting determines the data area size assigned to each
I/O module mounted on the base.
The data sent/received via CC-Link is mapped according to
this setting.
See "COMPONENT IDENTIFICATION" and "TRANSMIS-
SION DATA DESCRIPTIONS".
■ STATION NO., BAUD RATE, ETC.
See "COMPONENT IDENTIFICATION".
■ NETWORK SLOTS ON THE BASE
I/O 1
I/O 2
With Model R3-BS base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network Module(s) and Power Module are mounted basi-
cally at the right end though technically they could be
mounted in any position.
With Model R3-BSW base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
R3-NC1
I/O n
EM-8355 Rev.15 P. 1 / 8

Advertisement

loading

Summary of Contents for M-system R3-NC1

  • Page 1 (14 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation. Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. ■ WIRING If you have any problems or questions with the product, •...
  • Page 2: Component Identification

    SW2-8 SW SETTING DATA ALLOCATION * Refer to the specifications of the related series for the Data Allocation Type of I/O modules. EM-8355 Rev.15 P. 2 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3: Terminal Connections

    *Not provided with ‘No Power Supply’ type module. ■ EURO TYPE CONNECTOR TERMINAL (CC-Link) Applicable wire size: 0.2 to 2.5 mm (AWG24 to 12) Stripped length: 7 mm EM-8355 Rev.15 P. 3 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: Communication Cable Connections

    Module 7 Sixteen (16) data areas are available to the R3-NC1. Total data areas occupied by I/O modules must be within this limitation. Sixteen (16) data areas are available. Total data areas occupied by I/O modules must be within this limitation.
  • Page 5 RX(n+0) 1, RX(n+1) 1, RX(n+2) 1 Module 2 RX(n+0) 2, RX(n+1) 2, RX(n+2) 2 Module 3 RX(n+0) F, RX(n+1) F, RX(n+2) F Module 16 EM-8355 Rev.15 P. 5 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 6 Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn. Lower 16 bits Higher 16 bits EM-8355 Rev.15 P. 6 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 7 0 : OFF 1 : ON ■ PLC REDUNDANT SYSTEM (models: R3-NC1-x/W) Bit 0 of RY(n+1) is assigned to designate control system or standby system. Set this bit from the host PLC to switch from the PLC master control system to the standby system, or vice versa. The R3 module output (slave station) is controlled according to the bit combinations as shown in the table below.
  • Page 8 H0010 Station information (set for the number of connected modules.) H0002 H0020 *1. [Example] 14xx for model R3-NC1 xx =R3-NC1 Station address. EM-8355 Rev.15 P. 8 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...