■ CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE1
terminal to ground.
Caution: FE1 terminal is NOT a protective conductor termi-
nal.
V+
CAN_H
TO OTHER
Drain
DeviceNet
DEVICES
CAN_L
V–
PC CONFIGURATION
USB
JACK
+24V
POWER
0V
+
EXC. SUPPLY
FE1

WIRING INSTRUCTIONS

■ TENSION CLAMP TERMINAL
• POWER SUPPLY, EXCITATION SUPPLY CONNECTOR
Applicable wire size: 0.2 – 2.5 mm
Stripped length: 10 mm
• NETWORK CONNECTOR
Communication cable: Approved for DeviceNet
Stripped length: 10 mm
Recommended solderless terminal
AI0,25-10YE 0.25 mm
(Phoenix Contact)
2
AI0,34-10TQ 0.34 mm
(Phoenix Contact)
2
AI0,5-10WH 0.5 mm
(Phoenix Contact)
2
AI0,75-10GY 0.75 mm
(Phoenix Contact)
2
AI1-10RD 1.0 mm
(Phoenix Contact)
2
AI1,5-10BK 1.5 mm
(Phoenix Contact)
2
AI2,5-10BU 2.5 mm
(Phoenix Contact)
2
INTERNAL BUS
INTERNAL
POWER (5V)
EXC. SUPPLY (24V)
2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
R80ND2
EM-7035-B P. 6 / 10