External Dimensions; Connection Diagram; Wiring Instructions; Communication Cable Connection - M-system R8-NC3 Instruction Manual

Power/network module

Advertisement

EXTERNAL DIMENSIONS

CONNECTION DIAGRAM

DA
DG
TO OTHER
CC-LINK
DB
DEVICES
SLD
FE
PC CONFIGURATION
JACK
JACK
+24V
0V
+
FE1
Note: In order to improve EMC performance, bond the FE1
terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.

COMMUNICATION CABLE CONNECTION

MASTER CONNECTION
MASTER UNIT
TERMINATOR
DA
DB
DG
SLD
FG
unit: mm (inch)
50 (1.97)
INTERNAL BUS
INTERNAL
POWER (5V)
EXC. SUPPLY (24V)
blue
white
yellow
*1. Turn on the terminator DIP switch to activate the internal terminating resistor.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: + 81 ( 6 ) 6659-8201 Fax: + 81 ( 6 ) 6659-8510 E-mail: info@m-system.co.jp
[3 (.12)]
55 (2.17)

WIRING INSTRUCTIONS

■ TENSION CLAMP TERMINAL BLOCK
•   Power input, excitation supply
Applicable wire size: 0.2 - 2.5 mm
stripped length 10 mm
•   CC-Link
Transmission cable: Approved for CC-Link,
stripped length 10 mm
R8-NC3
DA
DB
DG
SLD
FE
R8-NC3
[4 (.16)]
DIN RAIL
(35 mm wide)
,
2
R8-NC3
DA
*1
DB
DG
SLD
FE
EM-9726 P. 4 / 7