Wiring Instructions - M-system R30TS4 Instruction Manual

Thermocouple input module (4 points, isolated)

Advertisement

WIRING INSTRUCTIONS

■ TIGHTENING TORQUE
Separable screw terminal wiring screw: 0.5 N·m
Separable screw terminal fixing screw: 0.5 N·m
■ SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.25 to 0.75 mm
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.
3 (.12) max.
12 (.47) max.
■ HOW TO REMOVE SEPARABLE SCREW TERMINAL
The terminal block is separable in two pieces. Evenly loos-
en two screws on top and bottom of the terminal block to
separate.
■ HOW TO ATTACH CJC SENSOR
In re-attaching once removed CJC sensor, connect it to ter-
minals +CJn and COMn as shown below.
A RTD is attached on the REAR surface of the CJC sensor.
In order to measure accurate reference junction tempera-
ture, be sure to connect the sensor to terminal COMn with
its upside FRONT surface.
+CJn
COMn
FRONT surface
2
3.2 (.13) dia.
RTD
CJC sensor
REAR surface
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
PC CONFIGURATOR
The following parameter items can be set with using PC
Configurator Software (model: R30CFG).
Refer to the users manual for the R30CFG for detailed op-
eration of the software program.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
SETTING RANGE
Unused setting
CH enabled
CH disabled
Input Type
K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-26)
N
U
L
P (Platinel II)
(PR)
Burnout
Upscale
Downscale
None
CJC
Enabled
Disabled
Unit
degC
degF
K
Fine zero adjustment
-320.00 – +320.00 (%)
Fine gain adjustment
-3.2000 – +3.2000
Zero base
-3 200.0 – +3 200.0
(degC, K)
-32 000 – +32 000
(degF)
Full base
-3 200.0 – +3 200.0
(degC, K)
-32 000 – +32 000
(degF)
Scaled range Zero
-32 000 – +32 000
Scaled range Span
-32 000 – +32 000
■ CHANNEL BATCH SETTING
PARAMETER
SETTING RANGE
Conversion rate
250 ms
500 ms
Simulate input
Normal input
Simulated data
R30TS4
DEFAULT
SETTING
CH enabled
K (CA)
Upscale
Enabled
degC
0.00 (%)
1.0000
0.0
0.0
0
10 000
DEFAULT
SETTING
500 ms
Normal input
EM-9002 Rev.2 P. 5 / 5