M-system R3-NM3 Instruction Manual

Modbus interface module, for temperature control module

Advertisement

Quick Links

INSTRUCTION MANUAL
MODBUS INTERFACE MODULE
(For temperature control module)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Network interface module ..................................................(1)
Terminating resistor (110 Ω, 0.25 W) .................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ HOT INSERTION/REMOVAL OF MODULES
• It is possible to replace the module with the power is sup-
plied. Be sure to replace it when the module is not com-
municating with a host, as it is possible to affect the sys-
tem. However, replacing multiple modules at once may
greatly change line voltage levels. We recommend that
you replace them one by one.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 120V AC rating: 85 – 132V, 47 – 66 Hz, approx. 20VA
200 – 240V AC rating: 170 – 264V, 47 – 66 Hz, approx. 20VA
24V DC rating: 24V ±10%, approx. 12W
■ GENERAL PRECAUTIONS
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base Model R3-BS, or Model R3-BSW
for free I/O address capability.
Before mounting the Network Interface Module onto the
Base, be sure to configure the module as explained below.
■ DATA ALLOCATION
The setting determines the data area size assigned to each
I/O module mounted on the base.
The data sent/received via Modbus is mapped according to
this setting.
See "COMPONENT IDENTIFICATION" and "MODBUS
I/O ASSIGNMENTS".
■ NODE ADDRESS & BAUD RATE, ETC.
See "COMPONENT IDENTIFICATION".
■ NETWORK SLOTS ON THE BASE
I/O 1
I/O 2
With Model R3-BS base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network Module(s) and Power Module are mounted basi-
cally at the right end though technically they could be
mounted in any position.
With Model R3-BSW base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
R3-NM3
I/O n
EM-8330 Rev.3 P. 1 / 9

Advertisement

Table of Contents
loading

Summary of Contents for M-system R3-NM3

  • Page 1 • The unit is designed to function as soon as power is sup- plied, however, a warm up for 10 minutes is required for Thank you for choosing M-System. Before use, please check satisfying complete performance described in the data contents of the package you received as outlined below.
  • Page 2: Component Identification

    Note: Be sure to set unused SW6-6 through 6-8 to OFF. always be set to ‘Main’ (OFF). DUAL COMMUNICATION MAIN (*) SW3-1 EM-8330 Rev.3 P. 2 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3 Refer to the software manual of R3CON for detailed operation. ■ NETWORK MODULE SETTING PARAMETER AVAILABLE RANGE DEFAULT SETTING Time (no communication time) 0.2 – 3200.0 (sec.) 3.0 (sec.) EM-8330 Rev.3 P. 3 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: Terminal Connections

    Stripped length: 7 mm COMMUNICATION CABLE CONNECTIONS MODBUS MODBUS INTERFACE INTERFACE MODULE MODULE HOST PC TERMINATOR Tx+ / Rx+ Tx– / Rx– Rx– EM-8330 Rev.3 P. 4 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 5 Contents of the diagnostic data (2 bytes) Change ASCII Input Delimiter Delimiter character of ASCII message Force Listen Only Mode Force the slave into Listen Only Mode EM-8330 Rev.3 P. 5 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 6: Modbus I/O Assignments

    Refer to the instruction manual of each I/O module for details. SLOT ADDRESS 2001 – 5000 5001 – 8000 8001 – 11000 11001 – 14000 44001 – 47000 47001 – 50000 EM-8330 Rev.3 P. 6 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 7 With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con- verted into 135. Minus temperature is converted into negative values, represented in 2’s complements. EM-8330 Rev.3 P. 7 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 8 Input 16 (Output 16) 0 : OFF 1 : ON ■ TEMPERATURE CONTROL DATA (model: R3-TC2) Refer to the instruction manual of the R3-TC2. EM-8330 Rev.3 P. 8 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 9 ‘0.’ Be sure to switch the setting back to ‘1’ before the communication is restored. 5) When both the main and the sub network modules are in communication, the output can be switched without delay. EM-8330 Rev.3 P. 9 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...