Wiring Instructions - M-system R3-PD16 Instruction Manual

One-shot pulse output module

Advertisement

■ CONNECTION DIAGRAM
INTERNAL BUS A
* INTERNAL BUS B
INTERNAL POWER
Numbers in italic indicate LED No.s assigned to the front panel LEDs.
* For dual redundant communication.

WIRING INSTRUCTIONS

■ SCREW TERMINAL
Torque: 0.5 N·m
■ SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.3 – 0.5 mm
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.
3max
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
1
1
Do 1
2
2
Do 2
3
3
Do 3
4
4
Do 4
5
5
Do 5
6
6
Do 6
7
7
Do 7
8
8
Do 8
9
11
Do 9
10
12
Do 10
11
13
Do 11
12
14
Do 12
13
15
Do 13
14
16
Do 14
15
17
Do 15
16
18
Do 16
9
COM
10
COM
19
COM
20
COM
2
4min
3.2 dia.
12max
(mm)
FUNCTIONS
■ OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from
the preferred bus A.
When an error is detected, the output is switched to the
data from the bus B.
• Output Hold
If both are in error, the module holds the signal and
stands by until one of the communications recovers.
• Output OFF
If both are in error, the module outputs OFF signals and
stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is
established and normal data is received.
R3-PD16
EM-8395 Rev.3 P. 9 / 9