Troubleshooting; Stainless Steel Process Connection (Integral Cable) - Siemens Pointek CLS100 Operating Instructions Manual

Point level switches
Hide thumbs Also See for Pointek CLS100:
Table of Contents

Advertisement

Troubleshooting

5.1

Stainless steel process connection (integral cable)

Symptom
Green LED off
Green LED off, with proper sup-
ply
Green LED on and Yellow LED on
while not responding to product
and/or adjustment.
Hysteresis region too great.
Unequal current in red and black
wire.
Yellow LED won't come on or
off.
Too much current in loop
Red LED lights opposite to the
Yellow LED when this is not
meant to happen.
Red and Yellow LEDs are blink-
ing fast.
Red and Yellow LEDs are blink-
ing while switching.
Solid state contact does not
follow status Red LED.
Yellow LED is lit while probe is
not covered.
20
Cause
Proper power not applied to
device.
Power range must equal 12 to
33 V DC at all times (10 to 30 V
DC for IS versions).
Defective component in device.
Proper power not applied to
device.
Power range must equal 12 to
33 V DC at all times (10 to 30 V
DC for IS versions).
Proper power not applied to
device.
Power range must equal 12 to
33 V DC at all times (10 to 30 V
DC for IS versions).
Loop circuitry is DC biased w.r.t.
ground.
Black wire exceeds + 36 V DC
against Ground.
Defective component in device.
Supply voltage too high
Incorrect polarity on red and
black loop terminals.
Proper power not applied to
device.
Power range must equal 12 to
33 V DC at all times (10 to 30 V
DC for IS versions).
Proper power not applied to
device.
Power range must equal 12 to
33 V DC at all times (10 to 30 V
DC for IS versions).
Defective component in device.
Probable cause: wrong wiring in
this circuit.
May indicate significant product
buildup.
Compact Operating Instructions, 05/2021, A5E32146158-AB
Action
Check power source.
Minimum 12 V DC on the termi-
nals when the signal current is
20 mA (minimum 10 V DC for IS
versions)
Contact distributor
Check power source.
Minimum 12 V DC on the termi-
nals when the signal current is
20 mA (minimum 10 V DC for IS
versions)
Check power source.
Minimum 12 V DC on the termi-
nals when the signal current is
20 mA (minimum 10 V DC for IS
versions)
Correct loop circuitry.
Remove cause of voltage on the
red wire and/or bias.
Contact distributor
Ensure power range equals 12
to 33 V DC at all times (10 to 30
V DC for IS versions).
Reverse polarity on loop termi-
nals.
Check power source.
Minimum 12 V DC on the termi-
nals when the signal current is
20 mA (minimum 10 V DC for IS
versions)
Check power source.
Minimum 12 V DC on the termi-
nals when the signal current is
20 mA (minimum 10 V DC for IS
versions)
Contact distributor
Rotate sensitivity potentiometer
further CCW (counter clockwise)
Check sensor tip.
Pointek CLS100
5