Configuration
1. Immerse the sensor in the material that has the lowest dielectric constant. The yellow LED
should be ON.
2. Adjust the trimpot CCW until the yellow LED goes OFF.
3. Immerse the sensor in the material that has the highest dielectric constant; the yellow LED
should come ON.
Note
In areas with high levels of EMI, the sensitivity potentiometer should be turned back two
turns counter-clockwise after the setpoint is adjusted. After completing the setup, replace the
trimpot cap on the cable version, or the lid on the enclosure version. The unit is now in
service, providing level detection of your process.