5.4 Programming mode

The parameters can be modified using the front keypad. Access differs
according to the level: User (accessible without password), Service
(password=PW1) and Manufacturer (password = PW2). Press Prg to
access the main menu.
Main menu
A.On/Off Unit
B.Setpoint
C.Clock/Scheduler
Main menu icons
A.
Unit On/Off
B.
Set point
C.
Clock/scheduler
D.
Main/ Secondary
(future uses)

5.5 Setting/displaying the user parameters

The user parameters (A...F) are all the parameters accessible without
password, and include the following categories:
A: Unit ON/OFF: enable power-on from keypad, enable Autotest and
manual washing, set maximum production.
B: Set point: if Fa01 is set to control with probe (+ limit humidity probe),
the screen will show the humidity/temperature set point (+limit humidity
set point);
C: Clock/scheduler: set the current time and date (C01), the date for
changeover from standard time to daylight saving time and vice-versa
(C02), the daily time bands (C03) with weekly programming: up to 3
daily time bands can be set with independent set points. See example
2 described below.
D: Main-Secondary network configuration: Reserved.
E: Alarm log: the alarm log contains all the alarms, both active ( ) and
already reset ( ). The display can include up to 50 alarms with progressive
numbering, time and date of activation.
F: User: select the type of control and related parameters, enable washing
and activation mode, general settings for restart times, alarm relay logic,
drain valve in standby. See the chapter on "Functions".
EXAMPLE 1: Setting the current time/date.
1.
press Esc one or more times to move to the standard display;
2.
press Prg: the display shows the main menu;
3.
press UP/DOWN to move to category C. Clock/scheduler;
4.
press Enter to display the first screen: C01;
5.
press Enter to modify the current time using UP/DOWN; confirm by
pressing Enter and set the month and year;
6.
confirm by pressing Enter and set the hour/minutes;
7.
at the end of the settings, press Esc twice to exit the parameter setting
procedure.
"humiSonic ventilation" +0300063EN - rel. 1.3 - 14.05.2021
1/7
Fig. 5.c
E.
Alarm log
F.
User
G.
Service
Tab. 5.e
EXAMPLE 2: Setting the time bands and copying from one day to
another.
press Esc one or more times to move to the standard display;
press Prg: the display shows the main menu;
press UP/DOWN to move to category C. Clock/scheduler and Enter
again until reaching screen C03;
press Enter and enable the time bands (No
C04;
in screen C04:
a. press Enter and UP/DOWN to show the check sign for time band 1;
b. press Enter and UP/DOWN to select the day of the week. Confirm by
pressing Enter. Press UP/Down to uncheck the box. Press Enter to set
the band start hours and minutes and the status: OFF, ON, ON+SET
(ON+SET if control with probe selected). If ON, the set point selected
in screen B is shown, if ON+Set, set the desired set point;
c. once the time bands have been set for the day in question, press PRG
to copy the settings from one day to another.
Scheduler
Day:MON
07:00 ON
C
09:00 ON+SET
O
P
10:00 OFF
Y
--:-- ---
--:-- ---
--:-- ---

5.6 Setting the Service parameters

The Service parameters (letter G) concern:
a: change language;
b: information on: application, BIOS and BOOT version; flash memory and
RAM on the control board;
c: hour counter: operating hours in production and total unit operating
hours; maintenance interval setting.
To access the screens from d) on, the service password is needed -
PW1(0077).
d: BMS configuration: set BMS communication protocol (CAREL, Modbus),
communication speed, network address, enable control serial.
e:
Timings (Gea): set fill/drain times, refilling, production, delay for
water level or no communication alarms between control panel and
humidifier. See the chapter "Functions";
Delete alarm log (Geb), counter and restore default parameters;
Access management (Gec): interval of new Service password entry
when browsing, enable quick menu (On/Off and set point), enter User
password (PW0), change Service password (PW1).
f: Manual management: manual activation of fill/drain valves, group 1/2
(mist 1/2) of piezoelectric transducers, alarm relay, ambient and limit
probes.
Procedure: the setting/display procedure is similar to the one for the user
parameters, however password PW1 must be entered to access category
G parameters.
Note:
if no button is pressed, after around 5 min the display automatically returns
to standard mode;
the service password PW1 can be changed on screen Gec04 (and the main
password on screen Gec03);
once entered, the password remains active for a certain time, after which it
needs to be entered again.