Feedwater; Drain Water - Carel humiSonic User Manual

Ultrasonic humidiers
Hide thumbs Also See for humiSonic:
Table of Contents

Advertisement

2. Attach the pipes to the quick couplings (C) to connect the fi ll/drain
valves;
C
Fig. 2.d
Note: OD = 8 mm (5/16"), ID = 6 mm (15/64")
3. Reposition the cover, paying attention to the point of attachment (D).

2.5 Feedwater

To ensure correct operation, humiSonic requires the use of demineralised
water, with the chemical and physical characteristics specifi ed in the table.
To ensure these water quality values, a reverse-osmosis demineralisation
system is typically used.
FEEDWATER
Quick coupling
Temperature limits °C (°F)
Pressure limits bar (psi)
Specifi c conductivity at 20°C
Total hardness
Temporary hardness
Total quantity of dissolved solids (cR) Depending on specifi c conductivity
Dry residue at 180°C
Iron + manganese
Chlorides
Silicon dioxide
Chlorine ions
Calcium sulphate
Instant fl ow-rate l/min (gpm)
C
=0,65 * σ
(1) = in general
R
R,20 °C
To avoid excessive oversizing of the reverse osmosis system, it is
recommended to avoid sizing the system based on instant fl ow-rate.
Rather, an expansion vessel should be installed between the water
treatment system and humiSonic.
The sizing calculations need to consider discontinuous water
consumption, comprising the following stages:
fi lling (fi ll valve open);
production (fi ll valve closed);
washing (fi ll valve open).The table below suggests the minimum sizes
for connection to a generic reverse osmosis system.
Insert
Extract
1
2
D
Fig. 2.e
OD 8 mm (OD 5/16")
1...40 (33.8 to 104)
1...6 (14.5...87)
0...80 µS/cm
0...25 mg/l CaCO
3
0...15 mg/l CaCO
3
Depending on specifi c conductivity
0 mg/l Fe+Mn
0 to 10 ppm Cl
0 to 1 mg/l SiO2
0 mg/l Cl
mg/l CaSO4
0.6 (0.16)
Tab. 2.a
; R
= 0,93 * σ
180
R,20 °C
Model Storage
Total expansion l (gal) vessel volume
l (gal)
UU02
2,8 (0.62)
UU05
3,6 (0.79)
UU07
4,4 (0.97)
UU09
5,2 (1.14)
UU14
6,8 (1.50)
UU18
8,0 (1.76)
If no storage vessel is available, the reverse osmosis system must
guarantee the instant fl ow-rate of the fi ll SV, equal to 0.6 l/min (0.16 gpm).
Connecting humiSonic to the Carel WTS Compact (
American market)
The Carel product range includes a series of reverse osmosis systems
("WTS Compact") designed to produce water according to the feedwater
specifi cations and optimise connection to and operation with humiSonic
(see manuals +0300017 and +0300019).
All WTS Compact systems (P/N ROC%) always come with an expansion
vessel that maintains the required pressure in the circuit downstream.
Operation of the system is managed by pressure switches in the outlet
circuit. The basic rule for connection to the humidifi er is that the water
contained in the expansion vessel must be suffi cient to satisfy initial fi lling
and, if necessary, the washing cycle, while the WTS production time must
cover humiSonic production demand and fi ll the vessel as quickly as
possible.
The table below suggests the water consumption values and connections
for all sizes of humidifi ers.
Model
Prod.
Tank capac.
l/h (gph)
UU02
2,4 (0.63)
0,8 (0.18)
UU05
4,8 (1.27)
1,6 (0.35)
UU07
7,2 (1.90)
2,4 (0.53)
UU09
9,6 (2.53)
3,2 (0.70)
UU14 14,4 (3.80)
4,8 (1.06)
UU18
18 (4.76)
6,0 (1.32)
(*) Water consumption during the washing cycle is calculated based on
the default settings (1 wash every 12 hours, lasting 1 minute, which ends
by totalling fi lling and emptying the volume of the tank). Consumption
depends on the fi ll solenoid valve fl ow-rate, which is 0.6 l/min (0.16 gpm).
The duration and frequency of the washing cycles are parameters that
can be set by the user, and these have a signifi cant impact on the sizing
of the WTS system.
Important :
1. do not add disinfectants or anticorrosive compounds to the water, as
these are potential irritants;
2. the use of well water, industrial water or water from cooling
circuits and, in general, any potentially chemically or bacteriologically
contaminated water is prohibited.
(1)
(1)

2.6 Drain water

This is not toxic and can be drained into the sewerage system, as defi ned
by directive 91/271/EEC on urban waste-water treatment.
DRAIN WATER
Quick coupling
Typical temperature °C (°F)
11
(pre-charge 1.5 bars/22 psi)
11,2 (2.46)
14,4 (3.17)
17,6 (3.87)
20,8 (4.56)
27,2 (5.98)
32,0 (7.04)
Wash (*)
Code WTS
l (gal)
l/h (gph)
only for not
(
American
market)
)
2,8 (0.74)
ROC025500N
3,6 (0.95)
ROC025500N
4,4 (1.16)
ROC025500N
5,2 (1.37)
ROC025500N
6,8 (1.80)
ROC025500N
8,0 (2.11)
ROC025500N
OD Ø 8 mm (OD 5/16")
1 to 40 (33.8 to 104)
"humiSonic ventilation" +0300063EN - rel. 1.3 - 14.05.2021
ENG
Reverse osmosis
system l/h (gph)
5,2 (1.37)
8,4 (2.22)
11,6 (3.06)
14,8 (3.91)
20,8 (5.49)
26,0 (6.89)
Tab. 2.b
only for not
Additional
vessel
Not required
Not required
Not required
Not required
ROKC00KTVE
ROKC00KTVE
Tab. 2.c
Tab. 2.d

Advertisement