Samson TROVIS 3730-1 Translation Of Original Instructions page 137

Electropneumatic positioner
Hide thumbs Also See for TROVIS 3730-1:
Table of Contents

Advertisement

Code
Reading/values
P10
Control response
[PID]/PD
P11
Pressure limitation
ON/[OFF]
P12
Set point cutoff
decrease (end position
w <)
[ON]/OFF
P13
Set point cutoff increase
(end position w >)
ON/[OFF]
P14
Switching mode of soft-
ware limit contact
[NO.NO]
P15
Switching threshold of
software limit contact 1
–20 to 120 % [2 %]
EB 8484-1 EN
The integral action in the control parameters can be deactivated.
The signal pressure can take on the same pressure as the supply air
at the maximum [OFF] or, in the case that the maximum actuator
force can damage the valve, the pressure is limited to approx.
2.4 bar [ON].
Lower tight-closing function:
If w reaches up to 1 % towards the final value that causes the
valve to close, the actuator is immediately completely vented (with
ATO: air to open) or filled with air (with ATC: air to close).
Upper tight-closing function:
If w reaches up to 99 % towards the final value that causes the
valve to open, the actuator is immediately completely filled with air
(with ATO: air to open) or vented (with ATC: air to close).
Switching mode of software limit contact 1 (SLS1) and 2 (SLS2)
when activated (when the positioner has been initialized).
Explosion-protected version according to EN 60947-5-6:
NO.NC: SLS1 Conductive
NO.NO: SLS1 Conductive
NC.NC: SLS1 Non-conducting SLS2 Non-conducting
NC.NO: SLS1 Non-conducting SLS2 Conductive
Version without explosion protection:
NO.NC: SLS1 Conductive
NO.NO: SLS1 Conductive
NC.NC: SLS1 Non-conducting SLS2 Non-conducting
NC.NO: SLS1 Non-conducting SLS2 Conductive
When the positioner has not been initialized, the signal states of
the software limit contacts are the same as in the state of no re-
sponse.
If there is no mA signal at the terminals 11/12, both software limit
contacts switch to the non-conducting state.
Software limit 1 is displayed or can be changed in relation to the
operating range (steps of 0.5 %).
The contact switches to the responded state (Code P14) when the
value falls below the limit.
Annex A (configuration instructions)
Description
SLS2 Non-conducting
SLS2 Conductive
SLS2 Non-conducting
SLS2 Conductive
16-3