Malfunctions
Code Status Description
E4
Transit time too short
(initialization error)
Recommended action Check piping and re-initialize the positioner. Possibly
E5
Standstill detection is
not possible
(initialization error)
Recommended action Check supply air and positioner mounting.
E6
Travel is not achieved
during initialization
(initialization error)
Recommended action Check supply air, positioner mounting, lever, pin
E7
Actuator does not move
(initialization error)
Recommended action Check supply air, positioner mounting and mA input
E8
Travel signal at lower/
upper limit
Recommended action Reset error code (see section 9.1.1).
E9
Device error (internal)
to
E15
9-4
Cause/recommended action
Actuator transit times detected during initialization
are too short making optimal positioner tuning
impossible.
Minimum transit times:
K
= 25: ≥150 ms
P
K
= 50 to 100: ≥380 ms
P
use a screw restriction or reduce gain K
Supply pressure varies. Mounting incorrect.
Re-initialize the positioner.
Supply pressure is too low, actuator leaks, incorrect
travel adjusted or pressure limit function activated.
When MAX is selected for P5 code (nominal range):
the measuring span of the lever is too small (incorrect
lever, incorrect pin position). Initialization is canceled
when the angle of rotation of the positioner shaft is
smaller than 11°.
position and setting. Re-initialize the positioner.
No supply air, mounting blocked.
signal.
Re-initialize the positioner.
Wrong pin position, wrong lever, wrong attachment
direction when NAMUR attachment is used.
Check positioner mounting and re-initialize the
positioner.
Contact SAMSON's After-sales Service.
Class
2
.
P
2
2
2
1
1/3
EB 8484-1 EN