Operation; Block Diagrams - Omron S82K-00305 Manual

Ultimate din-track-mounting power supply with a wide power range from 3 to 240 w
Hide thumbs Also See for S82K-00305:
Table of Contents

Advertisement

New S82K

Operation

Undervoltage Alarm Indicator and Output Function
(All Models Except for S82K-24024/P24024)
If the output voltage at the output terminal drops to 75% to 90% of the rated voltage, the red indicator of the S82K (DC LOW indicator) will be lit. In
the case of the S82K-10024/24024T, a voltage drop alarm will be output via the relay available in the models (DC LOW output).
Note: This function detects the voltage at the output terminal of the Power Supply. To check the precise output voltage, measure the voltage
at the terminal of the load.
Indicator
Green:
DC ON
Red:
DC LOW
Green:
DC ON
(see note 1)
Red:
DC LOW
Green:
DC ON
Red:
DC LOW
Note: 1. The more the voltage at the output terminal drops, the darker both the green and red indicators will be.
2. The relay contacts have a capacity of 0.1 A at 24 VDC.

Block Diagrams

S82K-003jj (3 W)
S82K-007jj (7.5 W, Single Output)
Fuse (1 A)
AC (L)
AC (N)
S82K-007jj (7.5 W, Dual Outputs)
Fuse (1 A)
AC (L)
AC (N)
If the voltage at the output terminal is more than 90%
of the rated voltage, the green indicator will be lit.
If the voltage at the output terminal is 75% to 90%,
the red indicator will be lit.
If the voltage at the output terminal is 0 V, both the
green and red indicators will not be lit.
Noise filter
Inrush current
Rectifier
protection circuit
Drive control
circuit
Overload
alarm
circuit
Noise filter
Inrush current
Rectifier
protection circuit
Drive control
circuit
Overload
alarm
circuit
Voltage
Rectifier
Detector
Photocoupler
3-terminal
Rectifier
REG
Rectifier
Detector
Photocoupler
New S82K
Operation of 10024/ 24024T's
output (DC LOW output)
(see note 2)
+ V
– V
Undervoltage
alarm
indicator
Undervoltage
alarm
indicator
– V
+ V
11