Omron S82K-00305 Manual page 5

Ultimate din-track-mounting power supply with a wide power range from 3 to 240 w
Hide thumbs Also See for S82K-00305:
Table of Contents

Advertisement

New S82K
Item
Other
Ambient
temperature
Ambient
humidity
Dielectric
strength
Insulation
resistance
Vibration
resistance
Shock resistance
Screw tightening
torque
Output indicator
Electromagnetic
interference
(see note 1)
EMC
(see note 3, 4)
Approved
standards
Weight
Note: 1. Defined with a 100% load and the rated input voltage (100 or 200 VAC).
2. Do not press down on the terminal block with a force exceeding 75 N while tightening the terminals.
3. To ensure the emission ratings, a noise filter should be used on the output lines at the closest point.
(3- to 50-W models: S82Y-JF3-N, 90- and 100-W models: S82Y-JF6-N)
4. To ensure the Emission Enclosure rating, a ferrite ring core should be used on all cables (for S82K-P24024).
5. Models other than dual output models satisfy the Class-2 requirements.
6. To meet Class-2 requirements with the 100-W model, either a fuse or circuit breaker that is UL listed or CSA certified, and rated at
4.2 A max. should be wired in series with the load to be connected to the power supply. Only then can the power supply output be
considered as meeting Class 2.
8
Single output
Dual
outputs
3 W
7.5 W
7.5 W
Operating: See the derating curve in the Engineering Data section
(no condensation or icing)
Storage:
–25 C to 65 C (no condensation or icing)
Operating: 25% to 85%
Storage:
25% to 90%
3,000 VAC at 50/60 Hz for 1 min (between all inputs and outputs)
2,000 VAC at 50/60 Hz for 1 min (between all inputs and GR terminal)
1,000 VAC at 50/60 Hz for 1 min (between all outputs and GR terminal)
Alarm current: 10 mA (3- to 7.5-W models) 20 mA (15- to 100-W models) 25 mA (240-W models)
100 MΩ min. at 500 VDC (between all outputs and all inputs/GR terminal)
Malfunction: 10 to 55 Hz, 0.375-mm single amplitude for 2 hrs each in X, Y,
and Z directions
2
Malfunction: 300 m/s
, 3 times each in X, Y, and Z directions
0.74 N m max. (see note 2)
Yes (green)
Conforms to FCC class B
3 to 100-W Models
(EMI):
EN50081-1
Emission Enclosure:
EN55022 class B (equivalent to EN55011 class B)
Emission AC Mains:
EN55022 class B (equivalent to EN55011 class B)
Emission Output Ports: EN55022 class A (with a recommended optional filter) (see note 3)
240-W Models
(EMI):
EN50081-2
Emission Enclosure:
EN55011 class A (see note 4)
Emission AC Mains:
EN55011 class A (see note 4)
Harmonic Current:
EN61000-3-2 (only for S82K-P24024)
Common to All Models
(EMS):
EN50082-2
Immunity ESD:
EN61000-4-2: 4-kV contact discharge (level 2)
Immunity Burst:
EN61000-4-4: 2-kV power-line (level 3)
Immunity Surge:
EN61000-4-5: between 2-kV lines (except for 240-W models)
Class 2 (UL 1310)/Class 2 (CSA C22.2 No. 950) (see notes 5 and 6)
UL 508 (Listing)/1950
CSA C22.2 No.14/No.950, EN50178 (VDE0160), EN60950
Conforms to VDE0106/P100
150 g max.
260 g
max.
PFC
No
Single output
15 W
30 W
50 W
8-kV air discharge (level 3)
2-kV output line (level 4)
between 4-kV line and FG (except for 240-W models)
380 g
400 g
max.
max.
New S82K
90 W
100 W
240 W
Malfunction: 10 to
55 Hz, 0.15-mm single
amplitude for 2 hrs
each in X, Y, and
Z directions
Conforms to FCC class A
UL 508 (Listing)/1012
CSA C22.2 No.14, CSA
E.B. 1402C, EN50178
(VDE0160), EN60950
Conforms to
VDE106/P100
600 g max.
1,800 g
max.
Yes
(-P models)
240 W
2,200 g max.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents