Operating instructions - SBU IO-Link
Terminal assignment
X1.1 PE
X1.2 GND
X1.3 +24 V DC ±10%
X1.4
X1.5
X1.6
X1.7
X1.8
X1.9
X1.10
X1.11
X1.12
X2.1 GND
X2.2 +24 V DC
X2.3 Digital input 1
X2.4 Digital input 2
X2.5 Analog input 1
X2.6 Analog input 2
Page 31 of 50
Collective error
Valve is OPEN
Valve is CLOSED (Q) / IO-Link (C)
PE
PE
Solenoid valve GND
Solenoid valve GND
Solenoid valve 1 +24 V DC (max. 2,1 W)
Solenoid valve 2 +24 V DC (max. 2,1 W)
Voltage OK (green)
Voltage polarity reversed (red)
Collective error (red)
OPEN position (green)
CLOSED position
(green)
SV1 activated (green)
SV2 activated (green)
1)
M12-Class A Plug
X3.1
+24VDC
X3.2
Output Valve OPEN
X3.3
0V
X3.4
Output Valve CLOSED (Q) /
IO-Link (C)
X3.5
N.C.
Note:
1)
Voltage supply and output signals for the valve
position are identical as for X1. Parallel use of
these interfaces is not necessary and also not
permitted.
LED signalling