Operating instructions - SBU IO-Link
I02
Collective error
Errors are signalled by the flashing of the red Error LED and the switching of the Collective Error output
X1.6.
No error messages have any effect on the current program sequence.
The error is reset once the cause of the error has been rectified.
Errors – Cause – Remedial action
I03
Errors that can be signalled by the SBU IO-Link are:
Error
Cause
Runtime monitoring:
The set running time is exceeded.
Collective
error
Default value: 0 s (deactivated)
Max. switching cycles:
Max. set switching cycles reached.
Default value: 0 n (deactivated)
Temperature overrange / temperature
underrange
All error messages are deactivated with the setting value "0". Further logical links can be added or
deselected to the collective fault. More details are given in the IODD interface description.
Page 46 of 50
Remedial action
Check the following components:
-
Valve switched
-
Actuator function
Check compressed air supply
Check the position of the cam plate.
Check for jamming in the pipeline.
The fault is automatically reset as soon
as the repeated ride is within the time
tolerance.
Check the number of switching cycles
performed.
Reset or increase the counter.
Check environment of SBU IO-Link