BACNet Flow CoNtroller
NETWORKING & SETUP

Setting the Device Instance (Coupled MAC and DI)

Device Instance:
A Device Instance number identifies a device within an entire building, therefore giving it a unique number or Address,
much like a telephone ext. number. A building can have one telephone number, but all the extensions have a unique
number to identify them. A Device Instance number would work the same way and must be unique throughout the building.
Below is a table defining how a Device Instance number is obtained.
Note:
Each device on a network segment must be set to run at the same speed or baud rate.
Description
MAC Address
tier 1 (x100)
tier 2 (x10,000)
tier 3 (x1,000,000)
Example Device Instance setup with Default settings:
• MAC Address = 6 (6 x 1 = 6) – Set through software
+
tIer 1 = 58 (58 x 100 = 5800) – Set through software
+
tIer 2 = 1 (1 x 10,000 = 10,000) – Set through software
+
tIer 3 = 0 (0 x 1,000,000 = 1,000,000) – Set through software
=
Final Device Instance = 0,015,806