Service Menu - Bacnet; Service Menu - Diagnostics - Price BFC Series Manual

Flow controller for fan filter units
Hide thumbs Also See for BFC Series:
Table of Contents

Advertisement

BACNet Flow CoNtroller
DISPLAY NAVIGATION
Service Menu – BACnet
MAC ADDreSS
1
DeVICe INSt
0, 000, 101
BAUD rAte
76800
rS-485 terM,
DISABleD
reStore BACNet
DFltS
PreSS MeNU
to eXIt
Service Menu – Diagnostics
reStore
ttlDeV reSet
reStore
FACtorY CoNFIG
PreSS MeNU
to eXIt
Sets unit's MAC address
Note:
the MAC address (range 1-99) is added to the device instance.
Example: MAC address = 1, device instance = 100, total address for this BFC would be 101
This is the 'software' BACnet address and must be unique to your building site.
Range: 1 – 4,194,303
BAUD RATE
This sets the BACnet MS/TP baud rate
9600 baud (all BACnet devices must at least support this speed) – slowest
19200 baud
38400 baud
76800 baud (default baud rate for Price products) - fastest
Enable and disable RS-485 termination on MS/TP segment.
Reset MAC Address, Device Instance, and BAUD rate to default values.
Full device reset, removes all order information including unit configuration. Does not change any BACnet settings.
Resets device to factory settings without changing any BACnet settings.
priceindustries.com | BACNet FLow CoNtroLLer - Manual
9