Lochinvar EcoSword LGC 160-210 G P CE Installation, Commissioning, User & Maintenance Instructions page 77

Ecosword gas fired condensing water heater
Table of Contents

Advertisement

Code and description
F11 (blocking error)
Ionisation error
Ionisation measured with
a closed gas control valve
F19 (blocking error)
Supply voltage error
Three unsuccessful
ignition attempts.
F21 (lock out error)
Air proving switch error
Switch is not closed, while
fan runs during post purge
S02 (blocking error)
Sensor error
Open circuit from sensor 1
of the temperature sensor
S03 (blocking error)
Sensor error
Open circuit from sensor 2
of the temperature sensor
S12 (blocking error)
Sensor error
Short circuit in sensor 1 of
the temperature sensor
S13 (blocking error)
Sensor error
Short circuit in sensor 2 of
the temperature sensor
0312582_EcoSword_V4.0, 03-05-2021
Cause
Defective gas control valve.
There is not enough or too much supply
voltage during 60 seconds.
The measured voltage between live and
neutral must be 230 V
(-15%,
AC
+10%).
The supply voltage between live and
earth must be between 110 V
230 V
(-15%, +10%)
AC
Damaged wiring/open circuit.
Sensor is not (correctly) connected.
Damaged wiring and/or defective sensor. Replace the wiring and/or sensor.
Sensor is not (correctly) connected.
Damaged wiring and/or defective sensor. Replace the wiring and/or sensor.
Short circuit in the sensor circuit.
Short circuit in the sensor circuit.
Measure
-
Make sure that there is no flame after
the gas control valve has closed.
-
If there is a flame, the gas control
valve must be replaced.
-
Make sure that the supply voltage on
the controller is correct.
-
If the supply voltage is above or below
the stated tolerance and the error
persists, contact your maintenance
and service engineer.
and
AC
-
Install an isolating transformer.
See measure of error F03 - Switch is not
closed when fan is running during pre-
purge.
-
Make sure that the connector is
connected to J3.
-
Make sure that the wire is connected
to the sensor.
-
Make sure that the connector is
connected to J3.
-
Make sure that the wire is connected
to the sensor.
Replace the wiring and/or sensor.
Replace the wiring and/or sensor.
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents