10
10.1
10.2
Parameter
Description
Turn the water heater on or off.
001
Setpoint ON-mode
002
Hysteresis
003
Turn setpoint EXT-mode (005)
004
on or off.
Setpoint EXT-mode 2
(2)
005
Actual water temperature
101/
102
Actual Ionisation signal
109
Status EXT contact
112
Status air proving switch
113
Actual fan speed
115
0312582_EcoSword_V4.0, 03-05-2021
Settings
Operator interface
The operator interface is parameter driven and enables the user to change parameters and
to verify the status and history of the water heater.
When you press [MENU] once, parameters 001 to 120 can be accessed. All other
parameters can be accessed when you press [MENU] for 10 seconds.
For more information about how to use the operator interface, refer to Operator interface
(see 3.1) and Set a parameter value (see 4.1).
Parameters
Unit/Value Adjustable
Off
ON
ºC
ºC
ENA
dIS
ºC
°C
μA
OPE
CLo
OPE
CLo
x10 rpm
Range
Yes
Off - water heater off
(OFF mode)
ON - water heater on
(ON mode)
Yes
40...max setpoint
Yes
2...15
Yes
ENA - Enable
dIS - Disable
Yes
40...max. setpoint
No
0...99
No
0...15
No
OPE - EXT contact open
CLo - EXT contact closed
No
OPE – air proving switch open
CLo - air proving switch closed
No
0...990
Default
Off
(1)
65
10
dIS
(1)
70
-
-
-
-
-
57