4. Restart the compute node remotely through the management interface.
5. If the problem remains, verify that any new software has been installed and configured correctly.
6. Contact your place of purchase of the software or your software provider.
Server is unresponsive (cannot press F1 to start System Setup)
Configuration changes, such as added devices or adapter firmware updates, and firmware or application
code problems can cause the server to fail POST (the power-on self-test).
If this occurs, the server responds in either of the following ways:
• The server restarts automatically and attempts POST again.
• The server hangs, and you must manually restart the server for the server to attempt POST again.
After a specified number of consecutive attempts (automatic or manual), the server to reverts to the default
UEFI configuration and starts System Setup so that you can make the necessary corrections to the
configuration and restart the server. If the server is unable to successfully complete POST with the default
configuration, there might be a problem with the system board.
Voltage system board fault is displayed in the event logs
Complete the following steps until the problem is solved.
1. Check BMC event logs and resolve the errors described in the event logs according to ThinkSystem
System Manager User Guide. See
.
guide.pdf
2. Update UEFI firmware and BMC firmware to the latest version.
3. Revert the system to the minimum configuration. See "Specifications" on page 3 for the minimally
required number of processors and DIMMs.
4. Restart the system.
• If the system restarts, add each of the items that you removed one at a time, restarting the system
each time, until the error occurs. Replace the item for which the error occurs.
• If the system does not restart, suspect the system board.
Unusual smell
Complete the following steps until the problem is solved.
1. An unusual smell might be coming from newly installed equipment.
2. If the problem remains, contact Lenovo Support.
Server seems to be running hot
Complete the following steps until the problem is solved.
Multiple compute nodes or chassis:
1. Make sure that the room temperature is within the specified range (see "Specifications" on page 3).
2. Check the management processor event log for rising temperature events. If there are no events, the
compute node is running within normal operating temperatures. Note that you can expect some
variation in temperature.
Cannot enter legacy mode after installing a new adapter
Complete the following procedure to solve the problem.
1. Go to UEFI Setup ➙ Devices and I/O Ports ➙ Set Option ROM Execution Order.
ThinkSystem SR635 Maintenance Manual
220