4.4 Notice on installation

Warning
Connecting the wallbox to the power supply other than as specifi ed in this section can
result in incompatibility of the installation as well as the risk of electric shock, and thus
cause damage to the wallbox, and injury or death.
▶ Only connect the wallbox to a power supply in a confi guration that is specifi ed in
this section.
Installation advice
Ground
Input
MCB
RCD
NOTE: For a TT or IT electric grid with 230 V from line to line, the charging station must be
installed with one phase being connected to clamp L1 and the other phase being connected
to clamp N.
NOTE: Make sure that the provided ground connection meets the local regulations. The
ground loss monitor functionality of the wallbox is limited to physical ground loss detection
and cannot detect quality.
26
TN-system
TT-system
IT-system
1-phase
3-phase
C-characteristic (MCB must be selected to match the
amperage settings of the charging station, considering MCB
manufacturer specifi cations)
40 A, 30 mA, AC Type A
PE-cable
Earth electrode installed
separately (to be installed)
230 V ± 10 %, 50 Hz
400 V ± 10 %, 50 Hz