■ Maintenance Forecast
(S8VS-@@@24A@)
Displays when the maintenance forecast has reached the set value.
Operation
Mode
The maintenance forecast
has reached the set value.
Maintenance
forecast
monitor
Output
voltage
Output
current
Peak-hold
current
http://www.ia.omron.com/
(See note.)
Remaining time
until replacement
Note: This indicator alternately
displays alarm (
)
and the maintenance
time until replacement.
■ Indication and Output
When the Product is purchased, "
electrolytic capacitors deteriorate, indication changes to "
ful
(Refer to page 19). "
" will be indicated for the maintenance
forecast display for approximately one month after the Power Supply
is first turned ON. The accumulated value will then be displayed
depending on the ambient conditions thereafter. (However, the "
indication may not appear, depending on the usage environment and
the set value for maintenance forecast.)
S8VS-06024A:
After the remaining time to maintenance is reduced to less than two
years, indication automatically changes to a value, which decreases
1.5
1.0
0.5
0.0
from "
" to "
" to "
" to "
increase. If the remaining time becomes less than 0.5 year, an alarm
a02
0.0
(
) and "
" are indicated alternately.
S8VS-09024A@/S8VS-12024A@,
S8VS-18024A@/S8VS-24024A@/S8VS-48024A:
If the maintenance forecast setting L (which can be set arbitrarily
from 0.0 to 5.0 years in 0.5-year steps) is set to a value larger than
two years, the indication automatically changes to a value (L - 0.5)
after the remaining time to maintenance is reduced to the set years,
a02
and an alarm (
) and the remaining time are indicated alternately.
If the setting is less than 2.0 years, the indication changes to a value
(1.5) after the remaining time becomes less than two years, and after
the remaining time becomes less than the set time, an alarm (
and the remaining time (L - 0.5) are indicated alternately.
a02
If the alarm (
) and a numeric value are indicated alternately, a
transistor (maintenance forecast output terminal (Yrs)) will turn OFF
to indicate the need for maintenance. (The transistor turns OFF
when the maintenance forecast time is reached, i.e., there will be no
continuity at the maintenance forecast output terminal.)
Note: 1. The remaining time to maintenance is based on continuous
operation, not including the time when the power supply is
turned OFF.
ful
2. "
" will be indicated until approximately one month of
time is accumulated to estimate the speed of deterioration
and the output will remain ON (continuity at the
maintenance forecast output terminal (Yrs)).
3. For details on the display, refer to Relationship between
Indicated Values and Output of Set Values under
Maintenance Forecast Monitor Function on page 19.
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
S8VS
ful
" will be indicated. As
hlf
"
hlf
" (year) as the running hours
a02
In the case that the
remaining time is
reduced to smaller
than 0.5 year and an
alarm is issued.
"
)